Point
No.
Point
Type
Point Name
Factory
Default
(SI Units)
Engr. Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On
Text
Off
Text
Z1000
Parameter
{60} LAO
INPUT REF
1
0 HZ 0.01 0
61 LAO
INPUT REF
2
0 HZ 0.01 0 d1-02
{62} LAI
PID
FEEDBACK
0 PCT 0.01 0 U5-01
63 LAO PID P GAIN 2 0.01 0 b5-02
64 LAO PID I TIM 0.5 SEC 0.1 0 b5-03
65 LDO
PID MODE
SEL
DISABLE 1 0 ENABLE DISABLE b5-01
{66} LAI
LST FLT
CODE
0 1 0 U2-02
{67} LAI FREF.FLT 0 HZ 0.01 0 U2-03
{68} LAI
OUT FREQ
FLT
0 HZ 0.01 0 U2-04
{69} LAI
OUT
CUR.FLT
0 AMPS (A) 0.01 0 U2-05
70 LAO
RD PARAM
NUM
1 1 0
71 LAI
RD PARAM
DAT
0 1 0
72 LAO
WR PARAM
NUM
1 1 0
73 LAO
WR PARAM
DAT
0 1 0
{74} LDI
MF IN 3
MON
OFF 1 0 ON OFF
UB-02 (Bit 4)
Bypass DI-5
{75} LAI
OUT
VOLT.FLT
0 VOLTS (V) 0.1 0 U2-07
{76} LAI
DC
BUS.FLT
0 VOLTS (V) 1 0 U2-08
{77} LAI
OUT
PWR.FLT
0 KW 0.1 0 U2-09
{78} LDI
MF IN 4
MON
OFF 1 0 ON OFF
UB-02 (Bit 5)
Bypass DI-6
{79} LAI
PID
DEVIATE
0 PCT 0.01 0 U5-02
80 LAO PID I LIMIT 100 PCT 0.1 0 b5-04
81 LAO
PID UP
LIMIT
100 PCT 0.1 0 b5-06
82 LAO
PID OFFS
ADJ
100 PCT 0.1 -100 b5-07
83 LAO
PID PRI
DYTM
0 SEC 0.1 0 b5-08
84 LAO
PID FB
RMDS
0 1 0 b5-12
85 LAO
PID FB
RMDL
0 PCT 1 0 b5-13
86 LAO
PID FB
RMDT
1 SEC 0.1 0 b5-14
{87} LAI
PID OUT
CAP
0 PCT 0.01 0 U5-14
{88} LAI PID REF 0 PCT 0.01 0 U5-04
{89} LAI
COMM ERR
CD
0 1 0 U1-19
90 LDO
COMM FLT
ENA
ENABLE 1 0 ENABLE DISABLE Z3-11