B.15 Defaults by Drive Model
The following tables show parameters and default settings that change with the drive model selection (o2-04).
Table B.4 208 V Default Settings by Model Selection
No. Name Unit Default Settings
Bypass Model Z1B1
D002
D003
D004
D007
D010
D016 D024 D031 D046 D059 D075
o2-04 Drive Model Selection Hex. 66 68 6A 6B 6D 6E 6F
b3-04 V/f Gain during Speed Search % 100 100 100 100 100 100 100
b3-06 Output Current 1 during Speed Search 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
0.50 0.50 0.50 0.50 0.50 0.50 0.50
b3-11
Speed Search Method Switching Level (Speed
Estimation Type)
5.0 5.0 5.0 5.0 5.0 5.0 5.0
C6-02 Carrier Frequency Selection 2 2 2 2 2 2 2
E2-01 Motor Rated Current A 10.60 16.70 24.20 30.80 46.2 59.4 74.8
E2-03 Motor No-Load Current A 3.00 4.50 5.10 8.00 11.2 15.2 15.7
L2-03
Momentary Power Loss Minimum Baseblock
Time
s 0.5 0.6 0.7 0.8 0.9 1 1
L2-05 Undervoltage Detection Level (Uv1) 190 190 190 190 190 190 190
L8-02 Overheat Alarm Level °C 80 80 105 105 110 110 115
L8-06 Input Phase Detection Level 16.0 21.0 15.0 18.0 22.0 23.0 24.0
L8-09 Output Ground Fault Detection Selection 0 0 0 0 0 0 1
L8-38 Carrier Frequency Reduction 2 2 2 2 2 2 2
No. Name Unit Default Settings
Bypass Model Z1B1 D088 D114 D143 D169 D211 D273
o2-04 Drive Model Selection Hex. 70 72 73 74 75 76
b3-04 V/f Gain during Speed Search % 100 80 80 80 80 80
b3-06 Output Current 1 during Speed Search 0.5 0.5 0.5 0.5 0.5 0.7
b3-08
Current Control Gain during Speed Search (Speed
Estimation Type)
0.50 0.50 0.50 0.50 0.50 0.50
b3-11
Speed Search Method Switching Level (Speed
Estimation Type)
5.0 5.0 5.0 5.0 5.0 5.0
C6-02 Carrier Frequency Selection 2 2 2 2 2 2
E2-01 Motor Rated Current A 88 114 143 169 211 273
E2-03 Motor No-Load Current A 18.5 21.9 38.2 44.0 45.6 72.0
L2-03 Momentary Power Loss Minimum Baseblock Time s 1 1.1 1.1 1.2 1.3 1.5
L2-05 Undervoltage Detection Level (Uv1) 190 190 190 190 190 190
L8-02 Overheat Alarm Level °C 115 115 109 109 109 109
L8-06 Input Phase Detection Level 24.0 25.0 28.0 26.0 28.0 28.0
L8-09 Output Ground Fault Detection Selection 1 1 1 1 1 1
L8-38 Carrier Frequency Reduction 2 2 2 2 2 2
B.15 Defaults by Drive Model
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual
351
B
Parameter List