C.5 Bypass Operations by BACnet
The bypass operations that can be performed by BACnet communication depend on parameter settings. This section explains
the functions that can be used and related parameter settings.
u
Observing the Bypass Operation
A controller can perform the following actions with BACnet communications at any time regardless of parameter settings:
Observe bypass and drive status and control terminal status from a controller
Read and write parameters
Set and reset faults
Set multi-function inputs.
Note:
Input settings from the input terminals So and from BACnet communications are both linked by a logical OR operation.
u
Controlling the Bypass
Select an external reference and adjust the parameters in Table C.1 accordingly to start and stop the drive or set the frequency
reference using BACnet communications.
Table C.1 Setting Parameters for Drive Control from BACnet
Reference Source Parameter Name Required Setting
External Reference 1
Z1-07 Frequency Reference Select 2
Z1-08 Run Command Select 2
Refer to Z1-07: Speed Reference Select on page 196 and Refer to Z1-08: Run Command Select on page 197 for details on
external reference parameter selections.
C.5 Bypass Operations by BACnet
362
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual