Yaskawa AC Drive Z1000 AC Drive HVAC Fan Manuale Utente

Navigare online o scaricare Manuale Utente per Apparecchiature Yaskawa AC Drive Z1000 AC Drive HVAC Fan. Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual Manuale Utente

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa

Sommario

Pagina 1 - 4 Option Components

YASKAWA AC Drive Z1000MANUAL NO. SIEP YAIZ1U 03AAC Drive for HVAC Fan and Pump Programming ManualModels: 600 V Class: 2 to 250 HPTo properly use the

Pagina 2 - Ports 1 and 2

Table of ContentsThis Page Intentionally Blank10YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

Pagina 3 - Power-Up Diagnostics

Setting 4: PM Derated Torque MotorUse this setting when operating a PM motor. PM motors for derated torque have a self-cooling design and the overload

Pagina 4 - W ARNING

Drive+V(+10.5V, 20 mA)Branch resistor12 kPTCthermistorA2 (0-10 V)ACJumper S1Terminal A1/A2Voltage/CurrentSelectionVIA2A1Figure 1.59 Connection of a Mo

Pagina 5 - Location

Setting 0: Ramp to StopThe drive stops the motor using the deceleration time 1 set in parameter C1-02.Setting 1: Coast to StopThe drive output is swit

Pagina 6 - <1>

Notes on Settings 1 and 2• “Uv” will flash on the operator while the drive is attempting to recover from a momentary power loss. A fault signal is not

Pagina 7 - 6 Procedure A

Amount of reduction = Slip frequency prior to KEB × (L2-08/100) × 2No. Name Setting Range DefaultL2-08 Frequency Gain at KEB Start 0 to 300% 100%nL2-1

Pagina 8 - Screw size: M3.5 to M6

The Stall Prevention level is automatically reduced in the constant power range. Refer to L3-03: Stall Prevention Limit during Acceleration on page 10

Pagina 9 - 6 Procedure A

• Also set parameter L3-03 when operating the motor in the constant power range.nL3-03: Stall Prevention Limit during AccelerationThe Stall Prevention

Pagina 10

Output FrequencyDeceleration characteristics when Stall Prevention wastriggered during deceleration Timespecified deceleration timeFigure 1.64 Stall P

Pagina 11

No. Name Setting Range DefaultL3-06 Stall Prevention Level During Run30 to 150 <1> <1><1> The upper limit and default for this sett

Pagina 12

nL3-20: DC Bus Voltage Adjustment GainDetermines the proportional gain used by overvoltage suppression (L3-11 = 1), Single Drive KEB 2 (L2-29 = 1), KE

Pagina 13 - (model specific)

Preface & General SafetyThis section provides safety messages pertinent to this product that, if not heeded, may result in fatality,personal injur

Pagina 14 - Figure 22 Connect the Option

nL3-25: Load Inertia RatioDetermines the ratio between the rotor inertia and the load. Set this parameter when using Single Drive KEB 2 (L2-29 = 1),In

Pagina 15

nL4-05: Frequency Reference Loss Detection SelectionThe drive can detect a loss of an analog frequency reference from input A1 or A2. Frequency refere

Pagina 16 - Line up tabs

Fault NameoC OvercurrentoH1 Drive OverheatoL1 Motor OverloadoL2 Drive OverloadoL3 Overtorque 1oL4 Overtorque 2Fault Nameov DC Bus OvervoltagePF Input

Pagina 17 - 7 Procedure B

Setting 1: Fault Output Is SetnL5-03: Time to Continue Making Fault Restarts (enabled only when L5-05 = 0)Although the drive will continue to execute

Pagina 18 - CVST31301

No. Name Setting Range DefaultL5-04 Fault Reset Interval Time 0.5 to 600.0 s 10.0 snL5-05: Fault Reset Operation SelectionNo. Name Setting Range Defau

Pagina 19

nL6-01: Torque Detection Selection 1The torque detection function is triggered when the current or torque exceed the levels set to L6-02 for longer th

Pagina 20 - 7 Procedure B

nL6-03: Torque Detection Time 1Determines the time required to trigger an alarm or fault after exceeding the level in L6-02.No. Name Setting Range Def

Pagina 21

nL8-02: Overheat Alarm LevelSets the overheat alarm (oH) detection level.The drive outputs an alarm when the heatsink temperature exceeds the overheat

Pagina 22 - Table of Contents

10 setc.time10 s 10 s 10 s 10 s 10 s 10 sfref × (L8-19)fref × (L8-19)2fref × (L8-19)4fref × (L8-19)3frefOutput frequencyReset oH AlarmReset oH AlarmDi

Pagina 23 - Mounting Tab

nL8-07: Output Phase Loss Protection SelectionEnables or disables the output phase loss detection triggered when the output current falls below 5% of

Pagina 24

i.1 PrefaceYaskawa manufactures products used as components in a wide variety of industrial systems and equipment. The selection andapplication of Yas

Pagina 25 - Figure 40 Wiring Diagram

nL8-15: oL2 Characteristics Selection at Low SpeedsSelects whether the drive overload capability (oL fault detection level) is reduced at low speeds t

Pagina 26 - 9 Option Drive Parameters

No. Name Setting Range DefaultL8-32 Main Contactor and Cooling Fan Power Supply Failure Selection 0 to 4 1Setting 0: Ramp to StopThe drive stops the m

Pagina 27 - 9 Option Drive Parameters

nL8-40: Carrier Frequency Reduction Off-Delay TimeSets a hold time before returning to the original carrier frequency setting after the carrier freque

Pagina 28

1.9 n: Special AdjustmentsThese parameters control a variety of specialized adjustments and functions, including Hunting Prevention, High Slip Braking

Pagina 29 - Output Frequency

un3: High Slip Braking (HSB) and Overexcitation BrakingnHigh Slip Braking (V/f)HSB works in V/f Control only and decreases the stopping time compared

Pagina 30 - 10 PROFINET Messaging

• Overexcitation Deceleration can be most efficiently used in a V/f Control.• Overexcitation Deceleration cannot be used with PM motors.Parameter Adju

Pagina 31

No. Name Setting Range Defaultn8-45 Speed Feedback Detection Control Gain 0.00 to 10.00 0.80nn8-47: Pull-In Current Compensation Time Constant (OLV/PM

Pagina 32

nn8-55: Load Inertia (OLV/PM)Sets the ratio between motor inertia and the inertia of the connected machinery. If this value is set too low, the motor

Pagina 33

1.10 o: Operator-Related SettingsThese parameters control the various functions, features, and display of the HOA keypad.uo1: HOA Keypad Display Selec

Pagina 34 - 11 Communication

no1-06: User Monitor Selection ModeNormally the monitors shown directly below the active monitor are the next two sequential monitors. If o1-06 (User

Pagina 35 - 11 Communication

uTrademarks• APOGEE® FLN is a registered trademark of Siemens Building Technologies, Inc.• APOGEE® Anywhere™ is a trademark of Siemens Building Techno

Pagina 36

No. Name Setting Range Defaulto1-10 User-Set Display Units Maximum Value 1 to 60000Determined byo1-03no1-11: User-Set Display Units Decimal DisplayDet

Pagina 37

uo2: HOA Keypad FunctionsThese parameters determine the functions assigned to the operator keys.no2-02: OFF Key Function SelectionDetermines if the OF

Pagina 38 - Cyclic Messaging

no2-06: Operation Selection when HOA Keypad is DisconnectedDetermines whether the drive will stop when the HOA keypad is removed in HAND mode or when

Pagina 39

no3-02: Copy Allowed SelectionAllows and restricts the use of the Copy function.No. Name Setting Range Defaulto3-02 Copy Allowed Selection 0, 1 0Setti

Pagina 40

no4-11: U2, U3 InitializationResets the fault trace and fault history monitors (U2-oo and U3-oo). Initializing the drive using A1-03 does not reset th

Pagina 41

1.11 S: Special ParametersuS1: Dynamic Audible Noise Control FunctionThe Dynamic Audible Noise Control Function reduces audible noise by suppressing t

Pagina 42

nS1-04: Voltage Restoration Complete LevelSets the level at which voltage restoration for the V/f pattern is complete as a percentage of the drive rat

Pagina 43 - Fault Buffer Mechanism

Sequence Timers 2 to 4These timers operate identically to Sequence Timer 1. Parameters S2-06 to S2-20 configure Sequence Timers 2 to 4.PriorityIf mult

Pagina 44 - 1 Preface and Safety

0:001:002:003:004:005:006:007:008:009:00Sequence Timer 3Run at d1-0310:0011:0012:0013:0014:0015:0016:0017:0018:0019:0020:0021:0022:0023:00Mon SunSatFr

Pagina 45

nS2-03/S2-08/S2-13/S2-18: Sequence Timers 1 to 4 Day SelectionSets the days for which sequence timers 1 to 4 are active.No. Name Setting Range Default

Pagina 46

i.2 General SafetyuSupplemental Safety InformationGeneral Precautions• The diagrams in this manual may be indicated without covers or safety shields t

Pagina 47

Setting 0: Operator (d1-01)Setting 1: Operator (d1-02)Setting 2: Operator (d1-03)Setting 3: Operator (d1-04)Setting 4: TerminalsSetting 5: Serial Comm

Pagina 48 -  Diagnostic and Alarms

nS3-03: Secondary PI Display DigitsSets the decimal place display for secondary PI units.No. Name Setting Range DefaultS3-03 Secondary PI Display Digi

Pagina 49

nS3-08: Secondary PI Integral Limit SettingSets the maximum output possible from the integrator.No. Name Setting Range DefaultS3-08 Secondary PI Integ

Pagina 50 - <1>

S3-13 PI2 Low Feedback Detection LevelPI2 Feedback (U5-18)S3-15 PI2 High Feedback Detection LevelOn-delay TimerOn-delay TimerS3-16 PI2 High Feedback D

Pagina 51 - Figure 44 Main Tab View

uS4: Bypass OperationThe Drive/Bypass functionality allows the drive to control contactors that switch the motor voltage source between the driveand l

Pagina 52 - Drive Status Tab

Fwd RunDrive Enable-Customer SafetiesOverride (Smoke Purge)Drive/Bypass SelectBP Drive Relay Contact OutputBAS InterlockBP Bypass Relay Contact Output

Pagina 53 - Network Tab

Fwd RunDrive Enable-Customer SafetiesOverride (Smoke Purge)Drive/Bypass SelectBP Drive Relay Contact OutputBAS InterlockBP Bypass Relay Contact Output

Pagina 54 - Email Alerts Tab

Fwd RunDrive Enable-Customer SafetiesOverride (Smoke Purge)Drive/Bypass SelectBP Drive Relay Contact OutputBAS InterlockBP Bypass Relay Contact Output

Pagina 55 - CAUTION

Fwd RunDrive Enable-Customer SafetiesOverride (Smoke Purge)Drive/Bypass SelectBP Drive Relay Contact OutputBAS InterlockBP Bypass Relay Contact Output

Pagina 56 - Figure 49 Doc Links Tab View

Fwd RunDrive Enable-Customer SafetiesOverride (Smoke Purge)Drive/Bypass SelectBP Drive Relay Contact OutputBAS InterlockBP Bypass Relay Contact Output

Pagina 57 - Configuration Tab

uSafety Messages DANGERHeed the safety messages in this manual.Failure to comply will result in death or serious injury.The operating company is respo

Pagina 58 - General Settings

No. Name Setting Range DefaultS4-02 BP Energy Save Bypass Trigger Level 0 to 20 Hz 0 HznS4-03: BP Energy Save Bypass TimerSets the time in seconds tha

Pagina 59 - Figure 53 Custom Tab View

Setting 0: Legacy Operation ModeWhen S5-04 = 0 (Legacy operation mode), the HAND/OFF/AUTO functionality for both the HOA keypad and multifunctioninput

Pagina 60 -  SI-EP3/V Firmware Update

Table 1.32 HAND/AUTO Multi-Function Inputs, Legacy Behavior (S5-04 = 0)AUTO Mode Selection(H1-oo = 6D)HAND Mode Selection(H1-oo = 6E)Frequency Referen

Pagina 61 - 13 Troubleshooting

uS6: Phase Order SelectionsnS6-01: Emergency Override SpeedSets the speed command used in emergency override mode when S6-02 = 0.No. Name Setting Rang

Pagina 62 - Minor Faults and Alarms

1.12 T: Motor TuningAuto-Tuning automatically sets and tunes parameters required for optimal motor performance.uT1: Parameter Settings during Inductio

Pagina 63 -  bUS Error Auto-Reset

nT1-07: Motor Base SpeedSets the motor rated speed according to the motor nameplate value. Enter the speed at base frequency when using a motorwith an

Pagina 64 - Related Parameters

nT2-06: PM Motor Rated CurrentEnter the motor rated current in amps.No. Name Setting Range DefaultT2-06 PM Motor Rated Current0.0% to 300.0% of thedri

Pagina 65 - 14 Specifications

nT2-15: Pull-In Current Level for PM Motor TuningSets the amount of pull-in current. Set as a percentage of the motor rated current.No. Name Setting R

Pagina 66 - Warning Contents

1.13 U: Monitor ParametersMonitor parameters let the user view various aspects of drive performance using the HOA keypad display. Some monitorscan be

Pagina 67 - 14 Specifications

Periodic Inspection & MaintenanceThis chapter describes the periodic inspection and maintenance of the drive to ensure that it receivesthe proper

Pagina 68

WARNINGInstall adequate branch circuit protection according to applicable local codes and this Installation Manual. Failureto comply could result in

Pagina 69 - YASKAWA AMERICA, INC

2.1 Section Safety DANGERElectrical Shock HazardDo not connect or disconnect wiring while the power is on.Failure to comply will result in death or se

Pagina 70 - 2 Product Overview

WARNINGDo not use improper combustible materials.Failure to comply could result in death or serious injury by fire.Attach the drive to metal or other

Pagina 71 - Quantity: 141

NOTICEDo not heat or throw the battery into fire.The battery remains in use even when power to the drive has been shut off. Be sure to also remove the

Pagina 72 - YASKAWA AC Drive Z1000

2.2 InspectionPower electronics have limited life and may exhibit changes in characteristics or performance deterioration after years of useunder norm

Pagina 73

uRecommended Periodic InspectionTable 2.2 outlines the recommended periodic inspections for Yaskawa drive installations. Although periodic inspections

Pagina 74

Inspection Area Inspection Points Corrective Action CheckedAir DuctInspect air intake and exhaust openings. They must befree from obstruction and prop

Pagina 75 - Parameter Details

2.3 Periodic MaintenanceThe drive has Maintenance Monitors that keep track of component wear. This feature provides advance maintenance warningand eli

Pagina 76 - L1-08: oL1 Current Level

nAlarm Outputs for Maintenance MonitorsAn output can be set up to inform the user when a specific components has neared its expected performance life.

Pagina 77

2.4 HOA Keypad Battery ReplacementThe HOA keypad contains a monitor battery that allows the user to check drive functions. The battery requires period

Pagina 78 - L2-29: KEB Method Selection

2.5 Drive Cooling FansNOTICE: Follow cooling fan replacement instructions. The cooling fan cannot operate properly when installed incorrectly and coul

Pagina 79

Parameter Details1.1 A: INITIALIZATION...181.2 B: APPLICA

Pagina 80

uCooling Fan Component NamesWARNING! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply can result

Pagina 81

uCooling Fan Replacement: 5A0006 to 5A0032WARNING! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comp

Pagina 82 - <1> <1>

ABCA – Push the connectors together sono space remains between themB – Label facing upC – Make sure the alignment pins lineup properlyFigure 2.6 Insta

Pagina 83

NOTICE: Follow cooling fan replacement instructions. Improper fan replacement could cause damage to equipment. Make sure the fan isfacing upwards when

Pagina 84 - Preface & General Safety

3.Install the replacement fan into the drive.Insert the fan at an angle so that it tilts towards the front of the drive. Next press down on the back o

Pagina 85 - Motor Inertia

nRemoving and Disassembling the Cooling Fan Unit1.Remove the terminal cover and front cover.2.Remove the fan connector (CN6).Remove the fan connectors

Pagina 86 - L5: Fault Restart

ACDBAC5A0062, 5A0077, 5A0099, 5A0125, 5A0145 5A0192, 5A0242A – Fan guardB – Cable coverC – Cooling fanD – Circulation fanFigure 2.17 Fan Unit Disassem

Pagina 87 - Auto-Restart - Cancel Early

Protective tube2.Insert the connector for fan B2 and guide the lead wire for fan B2 so the cable hook holds it in place.Insert the connector for fan B

Pagina 88 - L2-03 L2-03 L2-03

nInstalling the Cooling Fan Unit1.Reverse the procedure described above to reinstall the cooling fan unit.Figure 2.21 Install the Cooling Fan Unit: 5A

Pagina 89 - L6: Torque Detection

2.6 Drive ReplacementuServiceable PartsThe drive contains some serviceable parts. The following parts can be replaced over the life span of the drive:

Pagina 90

1.1 A: InitializationThe initialization group contains parameters associated with initial drive setup, including parameters involving the displaylangu

Pagina 91 - L8: Drive Protection

This section provides instructions for drive replacement only.To install option boards or other types of options, refer to the specific manuals for th

Pagina 92 - L8-02: Overheat Alarm Level

IG R+ R- S+ S- +V AC A1 A2 FM AM AC FE S1 S2 S3 S4 S5 S6 S7 SN SC SP +P M3 M4 M6 M1 M2 M5 MA MB MC Figure 2.26 Discon

Pagina 93 - Output frequency

2.6 Drive ReplacementThis Page Intentionally Blank182YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

Pagina 94

Parameter ListThis appendix contains a full listing of all parameters and settings available in the drive.A.1 UNDERSTANDING PARAMETER DESCRIPTIONS...

Pagina 95 - Terms and Abbreviations

A.1 Understanding Parameter DescriptionsuControl Modes, Symbols, and TermsThe table below lists terms and symbols used in this section to indicate par

Pagina 96

A.2 Parameter GroupsTable A.2 Parameter GroupsParameterGroupName PageA1 Initialization Parameters 186A2 User Parameters 186b1 Operation Mode Selection

Pagina 97

A.3 A: Initialization ParametersThe A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor

Pagina 98

A.4 b: ApplicationApplication parameters configure the source of the Run command, DC Injection Braking, Speed Search, timer functions, PIcontrol, Ener

Pagina 99 - 1.9 n: Special Adjustments

No.(Addr.Hex)Name LCD Display Description Values Pageb2-12(1BA)Short Circuit BrakeTime at StartSC Brake T@StartOLV/PMOLV/PMSets the time for Short Cir

Pagina 100

No.(AddrHex.)Name LCD Display Description Values Pageb3-27(1C9)Start Speed SearchSelectStart srch sel0: Start from 01: Start Fref>FminSelects a con

Pagina 101

Setting 5: Open Loop Vector Control for PMUse this mode when running a PM motor in variable torque applications that benefit from energy efficiency. T

Pagina 102

No.(Addr.Hex)Name LCD Display Description Values Pageb5-10(1AE)PI Output Gain Setting Output GainSets the gain applied to the PI output. Default: 1.00

Pagina 103

No.(Addr.Hex)Name LCD Display Description Values Pageb5-26(1E8)PI Maximum BoostTimeSetpointBoostTimSets the maximum boost time when PI feedback does n

Pagina 104

No.(Addr.Hex)Name LCD Display Description Values Pageb5-43(162)Custom PI OutputMonitor Setting 1PI Out MonMax U4Set maximum monitor value at maximum f

Pagina 105

A.5 C: TuningC parameters are used to adjust the acceleration and deceleration times, S-curves, torque compensation, and carrier frequencyselections.u

Pagina 106 - Trademarks

uC6: Carrier FrequencyNo.(Addr.Hex)Name LCD Display Description Values PageC6-02(224)Carrier FrequencySelectionCarrierFreq Sel1: 2.0 kHz2: 5.0 kHz3: 8

Pagina 107

A.6 d: ReferencesReference parameters set the various frequency reference values during operation.ud1: Frequency ReferenceNo.(Addr.Hex)Name LCD Displa

Pagina 108

ud3: Jump FrequencyNo.(Addr.Hex)Name LCD Display Description Values Paged3-01(294)Jump Frequency 1 Jump Freq 1Eliminates problems with resonant vibrat

Pagina 109

ud7: Offset FrequencyNo.(Addr.Hex)Name LCD Display Description Setting Paged7-01(2B2)Offset Frequency 1 Offset Freq 1Added to the frequency reference

Pagina 110

A.7 E: Motor ParametersuE1: V/f Pattern for Motor 1No.(Addr.Hex)Name LCD Display Description Values PageE1-01(300)Input Voltage Setting Input VoltageT

Pagina 111

<4> When Auto-Tuning is performed, E1-13 and E1-05 will be set to the same value.<5> Parameter ignored when E1-11 (Motor 1 Mid Output Freq

Pagina 112 - 1.11 S: Special Parameters

Copyright © 2014 YASKAWA AMERICA, INC. All rights reserved.No part of this publication may be reproduced, stored in a retrieval system, or transmitte

Pagina 113 - S2: Sequence Timers

Table 1.1 Parameters Not Changed by Drive InitializationNo. Parameter NameA1-00 Language SelectionA1-02 Control Method SelectionE1-03 V/f Pattern Sele

Pagina 114 - Examples of Sequence Timers

No.(Addr.Hex)Name LCD Display Description Values PageE5-09(331)Motor Induction VoltageConstant 1PM Mtr Ind V 1OLV/PMOLV/PMSets the induced peak voltag

Pagina 115

A.8 F: Communication Option ParametersuF6, F7: Communication Option CardParameters F6-01 through F6-03 and F6-06 through F6-08 are used for EtherNet/I

Pagina 116

No.(Addr.Hex)Name LCD Display Description Values PageF7-09(3ED)<6>Gateway Address 1 Gateway IP Add 1 Sets the most significant octet of network

Pagina 117

<5> When setting F7-13 to 0, all IP addresses (F7-01 to F7-04) must be unique.<6> When setting F7-13 to 0, also set parameters F7-01 to F7

Pagina 118 - Figure 1.75 PI2 Block Diagram

A.9 H Parameters: Multi-Function TerminalsH parameters assign functions to the multi-function input and output terminals.uH1: Multi-Function Digital I

Pagina 119

H1 Multi-Function Digital Input SelectionsH1-ooSettingFunction LCD Display Description PageF Through mode Term Not UsedSelect this setting when using

Pagina 120 - <2>

H1 Multi-Function Digital Input SelectionsH1-ooSettingFunction LCD Display Description Page40Forward run command(2-Wire sequence)FwdRun 2Wire SeqOpen:

Pagina 121

H1 Multi-Function Digital Input SelectionsH1-ooSettingFunction LCD Display Description Page70 Drive Enable2 Drive Enable 2Prevents the Drive from exec

Pagina 122 - Programmable Bypass Logic

uH2: Multi-Function Digital OutputsNo.(Addr.Hex)Name LCD Display Description Values PageH2-01(40B)Terminal M1-M2function selection(relay)M1-M2 Func Se

Pagina 123 - Emergency Override

H2 Multi-Function Digital Output SettingsH2-ooSettingFunction LCD Display Description Page20Drive overheat pre-alarm (oH)OH PrealarmClosed: Heatsink t

Pagina 124

Step Display/Result8.Use F1, F2, , and to enter the password.← →-PRMSET-A1- 05 = 1234(0~9999)“0”PRGSelect PasswordFWD49.Press to save what w

Pagina 125 - Figure 1.79 BAS Interlock

uH3: Multi-Function Analog InputsNo.(Addr.Hex)Name LCD Display Description Values PageH3-01(410)Terminal A1 SignalLevel SelectionTerm A1 Level0: 0-10V

Pagina 126 - Figure 1.80 Transfer on Fault

H3 Multi-Function Analog Input Settings H3-ooSettingFunction LCD Display Description Page4 Output voltage bias Voltage Bias 10 V = E1-05 (motor rated

Pagina 127

uH5: MEMOBUS/Modbus Serial CommunicationNo.(Addr.Hex)Name LCD Display Description Values PageH5-01(425)<1>Drive Slave Address Serial Comm AdrSel

Pagina 128

A.10 L: Protection FunctionL parameters provide protection to the drive and motor, including control during momentary power loss, Stall Prevention,fre

Pagina 129 - S5: HOA Keypad Parameters

No.(Addr.Hex)Name LCD Display Description Values PageL2-03(487)Momentary Power LossMinimum BaseblockTime PwrL Baseblock tSets the minimum wait time fo

Pagina 130

No.(Addr.Hex)Name LCD Display Description Values PageL3-05(493)Stall PreventionSelection during Run StallP Run Sel0: Disabled1: Decel time2: Decel tim

Pagina 131

uL4: Speed DetectionNo.(Addr.Hex)Name LCD Display Description Values PageL4-01(499)Speed AgreementDetection Level Spd Agree LevelL4-01 sets the freque

Pagina 132 - S6-03: ov2 Detect Time

uL6: Torque DetectionNo.(Addr.Hex)Name LCD Display Description Values PageL6-01(4A1)Torque DetectionSelection 1Torq Det 1 Sel0: Disabled1: OL Alm at S

Pagina 133 - 1.12 T: Motor Tuning

No.(Addr.Hex)Name LCD Display Description Values PageL8-07(4B3)Output Phase LossProtection Selection Outp Ph Loss Det0: Disabled1: 1PH Loss Det2: 2/3P

Pagina 134

A.11 n: Special AdjustmentThe n parameters adjust more advanced performance characteristics such as Hunting Prevention, speed feedback detection,High

Pagina 135

Step Display/Result7.Press and scroll to A1-02.← →-PRMSET- PRGControl MethodFWDA1-02= 0 0V/f Control 8.Press to display the value set to A1-

Pagina 136

un8: PM Motor Control TuningNo.(Addr.Hex)Name LCD Display Description Values Pagen8-45(538)Speed FeedbackDetection Control Gain PM Spd Fdbk GainOLV/PM

Pagina 137 - 1.13 U: Monitor Parameters

A.12 o: Operator-Related SettingsThe o parameters set up the HOA keypad displays.uo1: HOA Keypad Display SelectionNo.(Addr.Hex)Name LCD Display Descri

Pagina 138

No.(Addr.Hex)Name LCD Display Description Values Pageo1-15(3107)Frequency Referenceand Frequency RelatedMonitor Custom Units 3Fref Cust Unit 3Sets the

Pagina 139 - CAUTION

uo3: Copy FunctionNo.(Addr.Hex)Name LCD Display Description Values Pageo3-01(515)Copy Function SelectionCOPY SELECT0: COPY SELECT1: INV→OP READ2: OP→I

Pagina 140 - 2.1 Section Safety

A.13 S: Special ApplicationuS1: Dynamic Noise Control FunctionNo.(Addr.Hex)Name LCD Display Description Values PageS1-01(3200)Dynamic Audible NoiseCon

Pagina 141

No.(Addr.Hex)Name LCD Display Description Values PageS2-06(320B)Sequence Timer 2 StartTimeTmr 2 Start TimeSets the start time for timer 2. The value m

Pagina 142

No.(Addr.Hex)Name LCD Display Description Values PageS2-17(3216)Sequence Timer 4 StopTimeTmr 4 Stop TimeSets the stop time for timer 4. The value must

Pagina 143 - 2.2 Inspection

No.(Addr.Hex)Name LCD Display Description Values PageS3-05(321E)Secondary PI SetpointValuePI2 SetpointSets the secondary PI controller target valueDef

Pagina 144 - Periodic Inspection

uS4: Bypass OperationNo.(Addr.Hex)Name LCD Display Description Values PageS4-01(322B)BP Auto Transfer onFault EnableBP Fault Trnsfer0: Disabled1: Enab

Pagina 145

uS6: Z1000 ProtectionNo.(Addr.Hex)Name LCD Display Description Values PageS6-01(3236)Emergency OverrideSpeedE Override SpeedSets the speed command use

Pagina 146 - 2.3 Periodic Maintenance

nA2-33: User Parameter Automatic SelectionDetermines whether recently edited parameters are saved to the second half of the User Parameters (A2-17 to

Pagina 147 - Related Drive Parameters

A.14 T: Motor TuningEnter data into the following parameters to tune the motor and drive for optimal performance.uT1: Induction Motor Auto-TuningNo.(A

Pagina 148

No.(Addr.Hex)Name LCD Display Description Values PageT2-05(732)PM Motor RatedVoltageRated VoltageOLV/PMOLV/PMEnter the motor rated voltage as indicate

Pagina 149 - 2.5 Drive Cooling Fans

A.15 U: MonitorsMonitor parameters allow the user to view drive status, fault information, and other data concerning drive operation.uU1: Operation St

Pagina 150

No.(Addr.Hex)Name LCD Display DescriptionAnalogOutput LevelUnitU1-12(4B)Drive Status Int Ctl Sts 1Verifies the drive operation status.U1 - 12=0000000

Pagina 151

No.(Addr.Hex)Name LCD Display DescriptionAnalogOutput LevelUnitU2-07(86)Output Voltage atPrevious Fault Output VoltageDisplays the output voltage at t

Pagina 152

No.(Addr.Hex)Name LCD Display DescriptionAnalogOutput LevelUnitU3-23(300D)Time Hours and Minutesat Most Recent FaultFault 1 HHMM Displays the time whe

Pagina 153

uU4: Maintenance MonitorsNo.(Addr.Hex)Name LCD Display DescriptionAnalogOutput LevelUnitU4-01(4C)Cumulative OperationTimeDrv Elapsed TimeDisplays the

Pagina 154

No.(Addr.Hex)Name LCD Display DescriptionAnalogOutput LevelUnitU4-21(7DD)Run Command SourceSelectionRun Cmd SourceDisplays the source for the Run comm

Pagina 155

No.(Addr.Hex)Name LCD Display DescriptionAnalogOutput LevelUnitU5-18(302B)PI2 Feedback PI2 FeedbackDisplays the secondary PI feedback value. 10 V: Max

Pagina 156

A.16 Control Mode Dependent Parameter Default ValuesThe tables below list parameters that depend on the control mode selection. Changing the control m

Pagina 157

1.2 b: Applicationub1: Operation Mode Selectionnb1-01: Frequency Reference Selection for AUTO ModeSelects the frequency reference source 1.Note: If a

Pagina 158

A.17 V/f Pattern Default ValuesThe following tables show the V/f pattern setting default values depending on the control mode (A1-02) and the V/f patt

Pagina 159

A.18 Defaults by Drive ModelThe following tables show parameters and default settings that change with the drive model selection (o2-04).Table A.7 600

Pagina 160 - 2.6 Drive Replacement

No. Name Unit Default Settings– Model – 5A0041 5A0052 5A0062o2-04 Drive Model Selection Hex. CF D1 D2E2-11 Motor Rated Power kW (HP)30(40)37(50)45(60)

Pagina 161 - 1.1 A: Initialization

No. Name Unit Default Settings– Model – 5A0125 5A0145 5A0192 5A0242o2-04 Drive Model Selection Hex. D5 D6 D7 D9E2-11 Motor Rated Power kW (HP)90(125)1

Pagina 162

A.18 Defaults by Drive ModelThis Page Intentionally Blank244YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

Pagina 163

BACnet CommunicationsB.1 BACNET CONFIGURATION...246B.2 COMMUNICATION SPEC

Pagina 164

B.1 BACnet ConfigurationDrives can be monitored and controlled by a controller on a Building Automation and Control network (BACnet) using RS-485techn

Pagina 165 - Appendix: A

B.2 Communication SpecificationsBACnet specifications appear in the following table:Item SpecificationsInterfaceMS-TP (Master-Slave/Token-Passing)RS-4

Pagina 166 - Symbol Description

B.3 Connecting to a NetworkThis section explains how to connect the drive to a BACnet network and the network termination required for a connection.uN

Pagina 167 - A.2 Parameter Groups

uWiring Diagram for Multiple ConnectionsFigure B.3 explains the wiring diagrams for multiple connections using BACnet communication.nRS-485 InterfaceD

Pagina 168 - A2: User Parameters

Current InputInput terminals A1 and A2 can accept a current input signal. Refer to Table 1.6 to set terminals A1 and A2 for current input.Table 1.6 An

Pagina 169 - A.4 b: Application

B.4 BACnet Setup ParametersuBACnet Serial CommunicationThis section describes parameters necessary to set up BACnet communications.nH5-01: Drive Slave

Pagina 170

No. Name Setting Range DefaultH5-04 Stopping Method after CE 0 to 4 3Setting 0: Ramp to StopUses the deceleration time currently enabled.Setting 1: Co

Pagina 171

nH5-08: Communications Protocol SelectionSelects the communications protocol.No. Name Setting Range DefaultH5-08 Communications Protocol Selection 0 t

Pagina 172 - A1-03: Initialize Parameters

nH5-14, H5-15: BACnet Device Object Identifiers 0 and 1These parameters set the Instance Identifier of the BACnet Device Object, where the H5-14 value

Pagina 173

B.5 Drive Operations by BACnetThe drive operations that can be performed by BACnet communication depend on drive parameter settings. This sectionexpla

Pagina 174

B.6 Communications TimingTo prevent a communications overrun in the slave drive, the master should wait a certain time between sending messages tothe

Pagina 175

B.7 BACnet Objects SupporteduPresent Value AccessThe Present Value (PV) of BACnet objects can always be read. In addition, some PVs can be written or

Pagina 176 - A.5 C: Tuning

PropertyObject TypeDeviceAnalogInputAnalogOutputAnalogValueBinaryOutputBinaryOutputBinaryValueInactive_Text – – – – Yes Yes YesActive_Text – – – – Yes

Pagina 177

Object ID Object NameModbusAddressPrecision Range Units PV AccessAV12 Output Current 0042HXXXX.X(for drives ratedabove 11 kVA)XXX.XX(for drives rated1

Pagina 178 - A.6 d: References

uBinary Output ObjectsTable B.9 Binary Output ObjectsObject ID Object NameModbusAddressActive Text Inactive Text PV AccessBO1 MF Output M1-M2 0009H:bi

Pagina 179

Three inputs (Start-Stop-FWD/REV). Set A1-03 to 3330 to initialize the drive and preset terminals S1, S2, and S5 to thesefunctions. Refer to Setting 0

Pagina 180

Object ID Object NameModbusAddressActive Text Inactive Text PV AccessBV35 Frequency Agree 002CH:bit 2 ON OFF RBV36 Desired Frequency Agree 002CH:bit 3

Pagina 181 - A.7 E: Motor Parameters

B.8 Accessing Drive Parameters and the Enter CommanduReading Drive ParametersReading drive parameters not listed in the analog or digital objects is a

Pagina 182

B.9 Communication ErrorsErrors that may occur when accessing drive parameters using the BACnet objects are shown in Table B.12.Table B.12 MEMOBUS to B

Pagina 183

B.10 Self-DiagnosticsThe drive has a built-in self-diagnosing function of the serial communication interface circuits. To perform the self-diagnosisfu

Pagina 184 - Programming

B.11 BACnet Protocol Implementation Conformance StatementDate: 1/4/2011 Vendor Name: Yaskawa America, Inc.Product Name: AC Motor Controller ProductMod

Pagina 185

□Point-To-Point, EIA 232 (Clause 10), baud rate(s):□Point-To-Point, modem, (Clause 10), baud rate(s):□LonTalk, (Clause 11), medium:□Other:Device Addre

Pagina 186 - Parameter List

B.11 BACnet Protocol Implementation Conformance StatementThis Page Intentionally Blank266YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Pro

Pagina 187

APOGEE FLN (P1) CommunicationsC.1 APOGEE FLN SET-UP...268C.2 COMM

Pagina 188

C.1 APOGEE FLN Set-UpA Yaskawa America, Inc. representative is responsible for proper configuration of the drive for the primary application, whilea S

Pagina 189

C.2 Communication SpecificationsAPOGEE FLN specifications appear in the following table:Item SpecificationsInterfaceFLNRS-485Communication ParametersC

Pagina 190

Motor coastsDC Injection Braking with the current set in b2-02Run commandOutput frequencyON OFFMotor speedMinimum Baseblock Time (L2-03)Figure 1.4 D

Pagina 191

C.3 Connecting to a NetworkThis section explains how to connect the drive to an APOGEE FLN network and the network termination required for aconnectio

Pagina 192

uWiring Diagram for Multiple ConnectionsFigure B.3 and Figure E.4 explain the wiring diagrams for multiple connections using APOGEE FLN communication.

Pagina 193

uRecommended CableTable C.2 APOGEE FLN Cable SpecificationsSecification DescriptionCable configuration Twisted shielded pairGaugeStranded wire: 0.2 to

Pagina 194

C.4 Slope and Intercept ConversionSeveral drive parameters are available for monitoring purposes. The available parameters include FREQ OUTPUT (Point

Pagina 195 - Entry Accepted

nUnbundle the FeedbackTo unbundle the feedback (PI FEEDBACK) for monitoring in degrees Fahrenheit:New Intercept = 30New Slope = (Desired Range) x (Slo

Pagina 196 - Term A2 Offset

C.5 APOGEE FLN Point DatabaseThis section shows the APOGEE FLN point database for Application 2721.uAPOGEE FLN Point List SummaryThis database is for

Pagina 197 - H4: Analog Outputs

PointNumberPointTypePoint NameFactoryDefault(SIUnits)Eng. Units(SI Units)Slope(SIUnits)Intercept(SI Units)On Text Off Text Parameter35 <1>LDO RU

Pagina 198

PointNumberPointTypePoint NameFactoryDefault(SIUnits)Eng. Units(SI Units)Slope(SIUnits)Intercept(SI Units)On Text Off Text Parameter78 LDI MF IN 4 MON

Pagina 199 - A.10 L: Protection Function

C.6 Cable Loss Configuration and BehaviorThis section describes the configurable cable loss feature of the drive. This feature offers a user maximum f

Pagina 200

will be set. H5-04 = 0 selects Ramp to Stop. The deceleration time or the slope of the ramp is determined by the setting ofdrive parameter C1-02. H5-0

Pagina 201

Min output frequency100%(Max output frequency)Output frequency when Stop command was enteredRun wait time tActive deceleration timeMin Baseblock Time

Pagina 202

C.7 Mailbox FunctionsThis section defines the APOGEE FLN points that read and write drive parameters.uReading a Drive ParameterTwo points are defined

Pagina 203

C.8 TroubleshootingThis section describes the steps necessary to troubleshoot drive communications on an APOGEE FLN network.uTroubleshooting Checklist

Pagina 204

C.8 TroubleshootingThis Page Intentionally Blank282YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

Pagina 205 - A.11 n: Special Adjustment

Metasys N2 CommunicationsD.1 METASYS N2 SPECIFICATIONS...284D.2 COMMUNICATION SPE

Pagina 206

D.1 Metasys N2 SpecificationsDrives can be monitored and controlled by a controller on a Metasys N2 network (N2) using RS-485 technology. The drivesac

Pagina 207

D.2 Communication SpecificationsMetasys N2 specifications appear in the following table:Item SpecificationsInterface RS-485Communication ParametersCom

Pagina 208

D.3 Connecting to a NetworkThis section explains how to connect the drive to an N2 network and the network termination required for a connection.uNetw

Pagina 209

uWiring Diagram for Multiple ConnectionsFigure B.3 explains the wiring diagrams for multiple connections using N2 communication.nRS-485 InterfaceDrive

Pagina 210

D.4 N2 Setup ParametersuN2 Serial CommunicationThis section describes parameters necessary to set up N2 communications.nH5-01: Drive Slave AddressSets

Pagina 211 - A.13 S: Special Application

nH5-04: Stopping Method after Communication ErrorSelects the stopping method after a communications error (CE) has occurred.No. Name Setting Range Def

Pagina 212

Setting 0: StandardSetting 1: Switch Phase OrderThe direction of the motor is reversed.nb1-17: Run Command at Power UpDetermines whether an external R

Pagina 213

Setting 0: MEMOBUS/ModbusSetting 1: N2Setting 2: P1Setting 3: BACnetnH5-09: Communications Fault Detection TimeSets the time the communications must b

Pagina 214

nH5-14, H5-15: BACnet Device Object Identifiers 0 and 1Note: These parameters are ignored when N2 protocol is selected (H5-08 = 1).These parameters se

Pagina 215

D.5 Drive Operations by N2The drive operations that can be performed by N2 communication depend on drive parameter settings. This section explainsthe

Pagina 216

Loop GainPI Proportional Gain (AO 4) and PI Integral Time (AO 5) are the gain and integral time parameters used by the drive. The PIloop is structured

Pagina 217

Continue at Preset SpeedIn this mode, Cable Loss Timeout (AO 21) is set to the desired interval, Cable Loss Speed (AO 22) is set to the desired preset

Pagina 218 - A.14 T: Motor Tuning

D.6 Communications TimingTo prevent a communications overrun in the slave drive, the master should wait a certain time between sending messages tothe

Pagina 219

D.7 Metasys N2 Point DatabaseThis section describes the Metasys N2 point database. This database features 100 logical points: 38 Analog Inputs (AI), 3

Pagina 220 - A.15 U: Monitors

uMetasys N2 Analog Output (AO) SummaryTable D.5 Metasys N2 Analog Output Summary (Z1000 to Metasys N2)Object ID Object Name Units Default Value Z1000

Pagina 221

Object ID Object Name Default Off (0) State On (1) StateBI 10 Multi-Function Output 1 (H2-01) 0 Off OnBI 11 Multi-Function Output 2 (H2-02) 0 Off OnBI

Pagina 222

D.8 Mailbox FunctionuReading Drive ParametersTwo points are defined for reading drive parameters:• AO 30 – Specifies the parameter to be read from the

Pagina 223

Table of Contentsi. PREFACE & GENERAL SAFETY... 11i.1 Preface ...

Pagina 224

Output frequencyTimeDC Injection Brakingb2-04b2-13Short Circuit BrakingE1-09 Min. Frequencyb2-01 Zero Speed LevelFigure 1.9 Short-Circuit Braking at

Pagina 225

D.9 Self-DiagnosticsThe drive has a built-in self-diagnosing function of the serial communication interface circuits. To perform the self-diagnosisfun

Pagina 226

MEMOBUS/Modbus CommunicationsE.1 MEMOBUS/MODBUS CONFIGURATION...302E.2 COMMUNICATION SPECIFICA

Pagina 227

E.1 MEMOBUS/Modbus ConfigurationDrives can be controlled from a PLC or other master device via serial communications using the MEMOBUS/Modbus protocol

Pagina 228 - 1.2 b: Application

E.2 Communication SpecificationsMEMOBUS/Modbus specifications appear in the following table:Item SpecificationsInterface RS-422, RS-485Communications

Pagina 229

E.3 Connecting to a NetworkThis section explains how to connect the drive to a MEMOBUS/Modbus network and the network termination required for aconnec

Pagina 230 - A.18 Defaults by Drive Model

uWiring Diagram for Multiple ConnectionsFigure B.3 and Figure E.4 explain the wiring diagrams for multiple connections using MEMOBUS/Modbus communicat

Pagina 231

nRS-422 InterfaceR–R+S–S+IGPLCDriveDriveDriveS–S+R–R+IGS–S+R–R+IGS–S+R–R+IGS2OFFS2OFFS2ONFigure E.4 RS-422 InterfaceNote: 1. Set DIP switch S2 to the

Pagina 232

E.4 MEMOBUS/Modbus Setup ParametersuMEMOBUS/Modbus Serial CommunicationChanges to MEMOBUS/Modbus communications settings become effective after restar

Pagina 233

No. Name Setting Range DefaultH5-04 Stopping Method after CE 0 to 4 3Setting 0: Ramp to StopUses the deceleration time currently enabled.Setting 1: Co

Pagina 234 - Appendix: B

Setting 0: MEMOBUS/ModbusSetting 1: N2 (Metasys)Setting 2: P1 (APOGEE FLN)Setting 3: BACnetnH5-09: Communications Fault Detection TimeSets the time th

Pagina 235 - B.1 BACnet Configuration

nb2-13: Short Circuit Brake Time at StopThe Short Circuit Braking described for parameter b2-12 can also be applied at the end of deceleration to comp

Pagina 236 - Communications

E.5 Drive Operations by MEMOBUS/ModbusThe drive operations that can be performed by MEMOBUS/Modbus communication depend on drive parameter settings. T

Pagina 237 - B.3 Connecting to a Network

E.6 Communications TimingTo prevent a communications overrun in the slave drive, the master should wait a certain time between sending messages tothe

Pagina 238

E.7 Message FormatuMessage ContentIn MEMOBUS/Modbus communications, the master sends commands to the slave, and the slave responds. The messageformat

Pagina 239 - Selection

The example in Table E.2 shows the CRC-16 calculation of the slave address 02H and the function code 03H, yielding theresult D140H.Note: This example

Pagina 240 - B.4 BACnet Setup Parameters

E.8 Message ExamplesBelow are some examples of command and response messages.uReading Drive MEMOBUS/Modbus Register ContentsUsing the function code 03

Pagina 241 - H5-07: RTS Control Selection

uWriting to Multiple RegistersFunction code 10H allows the user to write multiple drive MEMOBUS/Modbus registers with one message. This processworks s

Pagina 242

E.9 MEMOBUS/Modbus Data TableThe tables below list all MEMOBUS/Modbus data.uCommand DataIt is possible to both read and write command data.Note: Bits

Pagina 243

Register No. Contents000FHControl Selection Settingbit 0 Reservedbit 1 PI Setpoint Inputbit 2, bit 3 Reservedbit 4 PI2 Target Input (enables the setti

Pagina 244 - Controlling the Drive

Register No. Contents0022HData Link Statusbit 0 Writing data or switching motorsbit 1Reservedbit 2bit 3 Upper or lower limit errorbit 4 Data conformit

Pagina 245 - B.6 Communications Timing

Register No. Contents002CHDrive Status 2bit 0 During Runbit 1 Zero Speedbit 2 Speed Agreebit 3 User Speed Agreebit 4 Frequency Detection 1bit 5 Freque

Pagina 246 - B.7 BACnet Objects Supported

Run commandOutput frequencyOutput currentOFF ONb3-02Decel time setset to b3-03Waits for twice as long as L2-04SelectedfrequencyreferenceMinimum Baseb

Pagina 247

Register No. Contents004BHDrive status (U1-12)bit 0 During Runbit 1 During Zero Speedbit 2 During Reverse Runbit 3 During Fault Reset Signal Inputbit

Pagina 248

Register No. Contents00C1HFault Contents 4bit 0 External Fault at input terminal S3 (EF3)bit 1 External Fault at input terminal S4 (EF4)bit 2 External

Pagina 249

Register No. Contents00C8HAlarm Contents 2bit 0 Undervoltage (Uv)bit 1 Overvoltage (ov)bit 2 Heatsink Overheat (oH)bit 3 Drive Overheat (oH2)bit 4 Ove

Pagina 250

Register No. Contents00CCHAlarm Contents 6bit 0 Output Voltage Detection Fault (VoF)bit 1 Reservedbit 2 Capacitor Maintenance Time (LT-3)bit 3 to C Re

Pagina 251 - Device Object

Register No. Contents00D9HoFA1o Contents (CN5)bit 0 Option RAM Fault (oFA10)bit 1 Option Operation Mode Fault (SLMoD) (oFA11)bit 2 Drive Receive CRC E

Pagina 252 - Enter Command Types

<3> Display is in the following units: 5A0007 to 5A0017: 0.01 A units; 5A0022 to 5A0242: 0.1 A units.<4> Set the number of motor poles to

Pagina 253 - B.9 Communication Errors

Fault Code Fault Name008EH Watchdog Circuit Exception (CPF13)008FH Control Circuit Fault (CPF14)0091H Clock Fault (CPF16)0092H Timing Fault (CPF17)009

Pagina 254 - B.10 Self-Diagnostics

uAlarm Register ContentsThe table below shows the alarm codes that can be read out from MEMOBUS/Modbus register 007FH.Table E.4 Alarm Register 007FH C

Pagina 255

E.10 Enter CommandWhen writing parameters to the drive from the PLC using MEMOBUS/Modbus communication, parameter H5-11 determineswhether an Enter com

Pagina 256

E.11 Communication ErrorsuMEMOBUS/Modbus Error CodesA list of MEMOBUS/Modbus errors appears below.When an error occurs, remove whatever caused the err

Pagina 257 - This Page Intentionally Blank

This feature injects the amount of DC current set to b3-06 to the motor and detects the speed by measuring the current feedback.The drive then outputs

Pagina 258 - Appendix: C

E.12 Self-DiagnosticsThe drive has a built-in self-diagnosing function of the serial communication interface circuits. To perform the self-diagnosisfu

Pagina 259 - C.1 APOGEE FLN Set-Up

IndexNumerics3-Wire Sequence...735th Most Recent Fault...

Pagina 260 - APOGEE FLN (P1)

Cooling Fan Maintenance ... 236Cooling Fan Maintenance Setting (Operation Time) ...

Pagina 261 - Setting 3: Coast with Timer

Frequency Reference Lower Limit ...57Frequency Reference Monitor Content During PI ...

Pagina 262 - C.3 Connecting to a Network

Middle Output Frequency Voltage 2...65Minimum KEB Time...

Pagina 263

ov Suppression Function Selection... 215PPassword and Password Setting ...

Pagina 264

S5: HOA Keypad Parameters ... 150Safety Circuit...

Pagina 265 - Conversion Example

Terminal Board ... 179Terminal Connections for Communication Self-Diagnostics. 263, 300,

Pagina 266 - Unbundle the Feedback

Revision HistoryThe revision dates and the numbers of the revised manuals appear on the bottom of the back cover.MANUAL NO. SIEP YAIZ1U 03APublished i

Pagina 268

When the number of maximum fault restarts in parameter L5-01 is set higher than 0, the drive will automatically performSpeed Search as specified by b3

Pagina 269

YASKAWA AMERICA, INC.2121 Norman Drive South, Waukegan, IL 60085, U.S.A.Phone: (800) YASKAWA (927-5292) or 1-847-887-7000 Fax: 1-847-887-7310http://

Pagina 270 - Continue at Preset Speed

nb3-06: Output Current 1 during Speed SearchSets the current injected to the motor at the beginning of Speed Estimation Speed Search as a factor of th

Pagina 271 - Drive Fault Numbers

No. Name Setting Range Defaultb3-19 Number of Speed Search Restarts 0 to 10 3nb3-24: Speed Search Method SelectionSets the Speed Search method.No. Par

Pagina 272

nTimer Function OperationThe timer function switches on when the timer function input closes for longer than the value set to b4-01. The timer functio

Pagina 273 - C.7 Mailbox Functions

If parameter b5-01 is set to 1 or 2, the frequency reference in b1-01 or one of the inputs listed in Table 1.8 becomes the PIsetpoint.If b5-01 is set

Pagina 274 - C.8 Troubleshooting

nPI Block DiagramFigure 1.16 PI Block Diagram1.2 b: ApplicationYASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual391Paramete

Pagina 275

1.6 F: Option Settings ...70F6: Communicat

Pagina 276 - Appendix: D

nb5-01: PI Function SettingEnables or disables the PI operation and selects the PI operation mode.No. Parameter Name Setting Range Defaultb5-01 PI Fun

Pagina 277 - D.1 Metasys N2 Specifications

nb5-09: PI Output Level SelectionReverses the sign of the PI controller output signal. Normally a positive PI input (feedback smaller than setpoint) l

Pagina 278 - Metasys N2

PI feedback valuePIFeedback Detection Loss Level(b5-13)PI FeedbackLoss Detection Time (b5-14)No FbLdetectionFbL detectionTimePI FeedbackLoss Detectio

Pagina 279 - D.3 Connecting to a Network

Setting 5: Feedback Loss FaultIf the PI feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a “FbL - Feedback Low

Pagina 280

The Snooze Function differs from the Sleep Function in that the feedback must drop below the level set to b5-24, PI SnoozeDeactivation Level, before n

Pagina 281 - D.4 N2 Setup Parameters

nb5-20: PI Setpoint ScalingDetermines the units for the PI Setpoint Value (b5-19) and monitors U5-01 and U5-04.No. Parameter Name Setting Range Defaul

Pagina 282

nb5-26: PI Maximum Boost TimeAssociated with the Snooze Function. In cases where the temporary PI Setpoint (intended PI setpoint + PI Setpoint Boost)c

Pagina 283

nb5-38, b5-39: PI Setpoint User Display, PI Setpoint Display DigitsWhen parameter b5-20 is set to 3, parameters b5-38 and b5-39 set a user-defined dis

Pagina 284

Setting 2: QuadraticThe monitor displays 1/(PI output)2Setting 3: CubicThe monitor displays 1/(PI output)3nb5-43/b5-44: Custom PI Output Monitor Setti

Pagina 285

Setting 1: Reverse EnabledNegative PI output will cause the drive to run in the opposite direction.nFine-Tuning PIFollow the directions below to fine

Pagina 286 - D.5 Drive Operations by N2

Recommended Periodic Inspection... 1642.3 Periodic Maint

Pagina 287

Setting 0: DisabledSetting 1: Enablednb8-04: Energy Saving Coefficient Value (V/f)Fine tunes Energy Saving control. Adjust this setting while viewing

Pagina 288

1.3 C: TuningC parameters set the characteristics for acceleration, deceleration, and S-curves. Other parameters in the C group cover settingsfor slip

Pagina 289 - D.6 Communications Timing

Output FrequencyC1-11Accel/Decel TimeSwitch FrequencyC1-03 settingWhen the output frequency C1-11, drive uses Accel/Decel Time 1 (C1-01, -02)When th

Pagina 290 - D.7 Metasys N2 Point Database

C2-02C2-010.20 s<1>0.20 s <1>C2-02C2-010.20 s <1>0.20 s <1>FWD runREV runOutputfrequency<1> S-Curve characteristic at De

Pagina 291

uC6: Carrier FrequencynC6-02: Carrier Frequency SelectionSets the switching frequency of the drive output transistors. Changes to the switching freque

Pagina 292

C6-03C6-04E1-04 x C6-05Output Frequency OutputFrequency Max Output FrequencyCarrier FrequencyFigure 1.22 Carrier Frequency Changes Relative to Outp

Pagina 293 - D.8 Mailbox Function

1.4 d: Reference SettingsThe figure below gives an overview of the reference input, selections, and priorities.=4=0=1=2=3b1-01(Freq.Reference Source1)

Pagina 294

Table 1.14 Multi-Step Speed Reference and Terminal Switch CombinationsReferenceMulti-Step SpeedH1-oo = 3Multi-Step Speed 2H1-oo = 4Jog ReferenceH1-oo

Pagina 295

Internal frequencyreference d2-01OperatingrangeFrequency Reference Upper LimitSet frequency referenceFrequency Reference Lower Limitd2-02Figure 1.25

Pagina 296 - D.9 Self-Diagnostics

FrequencyReference OutputFrequencyJump Frequency Width (d3-04)Jump Frequency 3 d3-03Jump Frequency 2 d3-02Jump Frequency 1 d3-01Frequency reference d

Pagina 297 - Appendix: E

A.9 H Parameters: Multi-Function Terminals ...204H1: Multi-Function Digital Input

Pagina 298 - Slave (Drive)

Power supplyForward Run / StopHold Accel/DecelFrequency referenceOutput frequencyd4-01 = 1d4-01 = 0Hold HoldOFFOFFOFFOFF OFFONON ONON ONONFigure 1.27

Pagina 299 - MEMOBUS/Modbus

ud7: Offset Frequencynd7-01 to d7-03: Offset Frequency 1 to 3Three different offset values can be added to the frequency reference. They can be select

Pagina 300 - E.3 Connecting to a Network

1.5 E: Motor ParametersE parameters cover V/f pattern and motor data settings.uE1: V/f Pattern for Motor 1nE1-01: Input Voltage SettingAdjusts the lev

Pagina 301

Setting Specification Characteristic Application8 50 Hz, Mid starting torqueHigh starting torqueSelect high starting torque when:• Wiring between the

Pagina 302

Predefined V/f Patterns for Models 5A0011 to 5A0077Table 1.20 Rated Torque Characteristics, Settings 0 to 3Setting = 0 50 Hz Setting = 1 60 Hz Setting

Pagina 303 - H5-01: Drive Slave Address

Table 1.25 Derated Torque Characteristics, Settings 4 to 7Setting = 4 50 Hz Setting = 5 50 Hz Setting = 6 60 Hz Setting = 7 60 Hz014.45751.3 25 50100.

Pagina 304 - H5-06 setting

Output Voltage (V)Frequency (Hz)E1-05E1-12E1-13E1-08E1-10E1-09 E1-07 E1-06 E1-11 E1-04Figure 1.29 V/f PatternNote: 1. The following condition must be

Pagina 305

nE2-04: Number of Motor PolesSet the number of motor poles to E2-04. If Auto-Tuning completes successfully, the value entered to T1-06 will automatica

Pagina 306 - Selected

• B-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the test report at 75 °C.• F-type insulation: Multiply 0.87 times the resi

Pagina 307

No. Parameter Name Setting Range DefaultE5-07 Motor q-Axis Inductance 0.00 to 600.00 mHDetermined byo2-04nE5-09: Motor Induction Voltage Constant 1 (K

Pagina 308 - E.6 Communications Timing

Network Cable Connection... 248Wiring Diagr

Pagina 309 - ERROR CHECK

1.6 F: Option SettingsuF6: Communication Option CardParameters F6-01 through F6-03 and F6-06 through F6-08 are used for EtherNet/IP and LONWORKS optio

Pagina 310 - (Lower) (Upper)

Setting 0: Multi-step Speed Operation DisabledMulti-step speed input frequency references are disabled when the NetRef command is selected.Setting 1:

Pagina 311 - E.8 Message Examples

1.7 H: Terminal FunctionsH parameters assign functions to the external terminals.uH1: Multi-Function Digital InputsnH1-01 to H1-07: Functions for Term

Pagina 312 - Writing to Multiple Registers

Setting Function PageA6 BP BAS Interlock 81A7 BP Customer Safeties 81A8 PI2 Disable (N.O.) 81A9 PI2 Disable (N.C.) 81AA PI2 Inverse Operation 81AB PI2

Pagina 313 - E.9 MEMOBUS/Modbus Data Table

Setting 7: Accel/Decel Time Selection 1Switches between accel/decel times 1 (C1-01 and C1-02) and 2 (C1-03 and C1-04). Refer to C1-01 to C1-04: Accel,

Pagina 314

Settings 10 and 11: Up/Down FunctionThe Up/Down function allows the frequency reference to be set by two push buttons when one digital input is progra

Pagina 315

Settings 12 and 13: Forward Jog, Reverse JogDigital inputs programmed as Forward Jog (H1-oo = 12) and Reverse Jog (H1-oo = 13) will be Jog inputs that

Pagina 316

Setting 19: PI DisableClose a digital input to indefinitely disable the PI function. When the input is released, the drive resumes PI operation. Refer

Pagina 317 - Max. output frequency

SettingTerminal Status <1>Detection Conditions <2>Stopping MethodN.O. N.C.AlwaysDetectedDetectedduring RunonlyRamp to Stop(fault)Coast to

Pagina 318

When an input terminal programmed for 42 closes, the drive will operate in the selected direction. The drive will stop whenthe input opens.The input p

Pagina 319

Writing to a Drive Parameter ... 280C.8 Troubl

Pagina 320

Setting 65, 66: KEB Ride-Thru 1 (N.C.), 2 (N.O.)Enables the KEB Ride-Thru function selected in parameter L2-29.DIgital Input FunctionDrive OperationIn

Pagina 321

Setting 70: Drive Enable2A digital input configured as a Drive Enable2 input (H1-oo = 70) prevents the drive from executing a Run command untilthe Dri

Pagina 322

Setting AC: PI2 Integral HoldLocks the value of the secondary PI controller integral value.Setting AD: Select PI2 ParametersUses the secondary PI cont

Pagina 323 - Fault Trace Contents

Setting Function Page15 Frequency Detection 3 8816 Frequency Detection 4 8817 Torque Detection 1 (N.C.) 861B During Baseblock (N.C.) 891E Restart Enab

Pagina 324

Setting 2: Speed Agree 1 (fref/fout Agree 1)Closes when the actual output frequency or motor speed is within the Speed Agree Width (L4-02) of the curr

Pagina 325

Status DescriptionOpen Output frequency or motor speed exceeded L4-01 + L4-02.Closed Output frequency or motor speed is below L4-01 or has not exceede

Pagina 326 - E.10 Enter Command

Setting 7: DC Bus UndervoltageThe output closes when the DC bus voltage or control circuit power supply drops below the trip level set in L2-05. A fau

Pagina 327 - E.11 Communication Errors

Setting 11: Fault Reset Command ActiveThe output closes when there is an attempt to reset a fault situation from the control circuit terminals, via se

Pagina 328 - Speed Search Activation

Frequency reference + L4-04Frequency reference – L4-04L4-03L4-03 + L4-04L4-03 – L4-04Frequency reference0 HzOFF OFFON ONFrequency referenceDuring Forw

Pagina 329 - E.12 Self-Diagnostics

L4-04Frequency Detection 4ONOFFL4-03Output Frequency or Motor SpeedFigure 1.48 Frequency Detection 4 Example with Positive L3-04 ValueRefer to L4-03,

Pagina 331

ONONOFFOFFONOFFONrun commandbaseblock commandoutput frequencyduring runduring frequency outputOFFFigure 1.49 During Frequency Output Time ChartSetting

Pagina 332

Setting 52: Sequence Timer 2 ActiveSequence Timer 2 is active.Setting 53: Sequence Timer 3 ActiveSequence Timer 3 is active.Setting 54: Sequence Timer

Pagina 333

uH3: Multi-Function Analog InputsThe drive is equipped with three multi-function analog input terminals: A1 and A2. Refer to Multi-Function Analog Inp

Pagina 334

H3-01 = 010 V5 V0 VGain = 200 %100 %Frequency referenceBias = 0 %E1-04Figure 1.50 Frequency Reference Setting by Analog Input with Increased Gain• Gai

Pagina 335

nH3-11, H3-12: Terminal A2 Gain and Bias SettingParameter H3-11 sets the level of the input value selected that is equal to 10 Vdc input or 20 mA inpu

Pagina 336

Setting 0: Frequency BiasThe input value of an analog input set to this function will be added to the analog frequency reference value. When the frequ

Pagina 337 - Revision History

Setting 7: Torque Detection LevelUsing this setting, the overtorque/undertorque detection level for torque detection 1 (L6-01) can be set by an analog

Pagina 338

No. Name Setting Range DefaultH4-01 Multi-Function Analog Output Terminal FM Monitor Selection 000 to 655 102H4-04 Multi-Function Analog Output Termin

Pagina 339

Gain = 100% Bias = 30%Gain = 100% Bias = 0%Gain 100% Bias 30%Gain 100% Bias 0%Monitor ValueMonitor Value0 V3 V10 V100%0%Output VoltageOutput VoltageH4

Pagina 340

1.8 L: Protection FunctionsuL1: Motor ProtectionnL1-01: Motor Overload Protection SelectionThe drive has an electronic overload protection function th

Commenti su questo manuale

Nessun commento