
6.9 Troubleshooting without Fault Display
This section describes troubleshooting problems that do not trip an alarm or fault.
The following symptoms indicate that the drive is not set correctly for proper performance with the motor. Refer to Motor
Performance Fine-Tuning on page 220 for guidance on troubleshooting.
• Motor hunting and oscillation
• Poor motor torque
• Poor speed precision
• Poor motor torque and speed response
• Motor noise
u
Common Problems
Common Problems Page
Cannot Change Parameter Settings 253
Motor Does Not Rotate Properly after Pressing the AUTO
Button or after Entering External Run Command
Motor Does Not Rotate 254
Motor Rotates in the Opposite Direction from the Run
Command
255
Motor Rotates in One Direction Only 255
Motor is Too Hot 255
oPE02 Error Occurs When Lowering the Motor Rated Current Setting 256
Motor Stalls During Acceleration or With Large Loads 256
Drive Frequency Reference Differs from the Controller Frequency Reference Command 256
Excessive Motor Oscillation and Erratic Rotation 257
Deceleration Takes Longer Than Expected 257
Noise From Drive or Motor Cables When the Drive is Powered On 257
Ground Fault Circuit Interrupter (GFCI) Trips During Run 257
Connected Machinery Vibrates When Motor Rotates
Unexpected Noise from Connected Machinery 257
Oscillation or Hunting 258
PI Output Fault 258
Motor Rotates After the Drive Output is Shut Off (Motor Rotates During DC Injection Braking) 258
Output Frequency is not as High as Frequency Reference 258
Sound from Motor 258
Motor Does Not Restart after Power Loss 259
u
Cannot Change Parameter Settings
Cause Possible Solutions
The drive is running the motor
(i.e., the Run command is present).
• Stop the drive and switch over to the Programming Mode.
• Most parameters cannot be edited during run.
The operator is not in the Parameter Setup Mode
(the screen will display “PAr”).
• See what mode the operator is currently set for.
• Parameters cannot be edited when in the Setup Mode (“STUP”). Switch modes so that “PAr”
appears on the screen. Refer to The Drive and Programming Modes on page 99.
A multi-function contact input terminal is set to allow
or restrict parameter editing
(H1-01 through H1-07 = 1B).
• When the terminal is open, parameters cannot be edited.
• Turn on the multi-function contact input set to 1B.
The wrong password was entered.
• If the password entered to A1-04 does not match the password saved to A1-05, then drive
settings cannot be changed.
• Reset the password.
If you cannot remember the password:
•
Scroll to Z1-02. Press
and simultaneously. Parameter Z1-03 will appear.
• Set a new password to parameter Z1-03.
6.9 Troubleshooting without Fault Display
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual
253
6
Diagnostics &
Troubleshooting
Commenti su questo manuale