Object ID Object Name
Modbus
Address
Active Text Inactive Text PV Access
BV17 Data Set Error 0020H:bit 4 ERROR OFF R
BV18 Overcurrent – Gnd Flt 0021H:bit 0 OC-GF OFF R
BV19 Main Ckt OverVoltage 0021H:bit 1 OV OFF R
BV20 Drive OverLoad 0021H:bit 2 OL2 OFF R
BV21 Drive OverHeat 0021H:bit 3 OH1-OH2 OFF R
BV22 Fuse Blown 0021H:bit 5 PUF OFF R
BV23 PI Feedback Loss 0021H:bit 6 FBL OFF R
BV24 External Fault 0021H:bit 7 EF0-EF OFF R
BV25 Hardware Error 0021H:bit 8 CPF OFF R
BV26 Mtr Ovrld-OvrTorque 0021H:bit 9 OL1-OL3 OFF R
BV27 OverSpeed 0021H:bit 10 OS-DEV OFF R
BV28 Main Ckt UnderVoltage 0021H:bit 11 UV OFF R
BV29 MCU Cntl Pwr Sy Err 0021H:bit 12 UV1-2-3 OFF R
BV30 Output Phase Loss 0021H:bit 13 LF OFF R
BV31 Communication Error 0021H:bit 14 CE OFF R
BV32 Operator Disconnect 0021H:bit 15 OPR OFF R
BV33 Operating 002CH:bit 0 OPERATING OFF R
BV34 Zero Speed 002CH:bit 1 ON OFF R
BV35 Frequency Agree 002CH:bit 2 ON OFF R
BV36 Desired Freq Agree 002CH:bit 3 ON OFF R
BV37 Frequency Detect 1 002CH:bit 4 ON OFF R
BV38 Frequency Detect 2 002CH:bit 5 ON OFF R
BV39 Drv Startup Complete 002CH:bit 6 ON OFF R
BV40 Low Voltage Detect 002CH:bit 7 ON OFF R
BV41 Base Block 002CH:bit 8 ON OFF R
BV42 Frequency Ref Mode 8785H:bit 8 COM LOCAL R
BV43 Run Command Mode 8485H:bit 9 COM LOCAL R
BV44 Over Torque Detect 002CH:bit 11 ON OFF R
BV45 Frequency Ref Lost 002CH:bit 12 ON OFF R
BV46 Retry Error 002CH:bit 13 ON OFF R
BV47 Modbus Comms Error 002CH:bit 14 ON OFF R
BV48 Modbus Timeout Error 002CH:bit 15 ON OFF R
BV49 CRC Error 003DH:bit 0 ON OFF R
BV50 Invalid Data Length 003DH:bit 1 ON OFF R
BV51 Parity Error 003DH:bit 3 ON OFF R
BV52 Overrun Error 003DH:bit 4 ON OFF R
BV53 Framing Error 003DH:bit 5 ON OFF R
BV54 Timeout Error 003DH:bit 6 ON OFF R
BV55
<1>
Parameter Accept 0910H:bit 0 ON OFF W
BV56
<1>
Parameter Enter 0900H:bit 0 ON OFF W
BV57 Drive Comms Error 002CH:bit 15 ON OFF R
BV58 BYP Run Fwd CMD 8400H: bit 0 ON OFF C
BV59 BYP Run Rev CMD 8400H: bit 1 ON OFF C
BV60 Not Used BV60 ON OFF R
BV61 BYP Xfer to BYP CMD 8400H: bit 3 ON OFF C
BV62 BYP Smok Prg BYP CMD 8400H: bit 4 ON OFF C
BV63 BYP Smok Prg DRV CMD 8400H: bit 5 ON OFF C
BV64 BYP Mtr OR Sel CMD 8400H: bit 6 ON OFF C
BV65 BYP Mtr AND Sel CMD 8400H: bit 7 ON OFF C
C.6 BACnet Objects Supported
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual
367
C
BACnet
Communications
Vedere la pagina 366