SGDV SERVOPACK
SGMJV/SGMAV/SGMPS/SGMGV/SGMSV/SGMCS Servomotors
Rotational Motor
MECHATROLINK-III Communications Reference
-V Series
AC Servo Drives
USER’S MANUAL
Design and Maintenance
MANUAL NO. SIEP S800000 64H
1
2
3
4
5
6
7
8
9
10
Outline
Wiring and Connection
Operation
Adjustments
Utility Functions (Fn)
Monitor Displays (Un)
Fully-closed Loop Control
Troubleshooting
Appendix
Panel Display and
Operation of Digital Operator
Vedere la pagina 0
1 2 3 4 5 6 ... 390 391

Sommario

Pagina 1 - -V Series

SGDV SERVOPACKSGMJV/SGMAV/SGMPS/SGMGV/SGMSV/SGMCS ServomotorsRotational MotorMECHATROLINK-III Communications Reference-V SeriesAC Servo DrivesUSER’S

Pagina 2

x Operation Maintenance and Inspection Disposal CAUTION• Always use the servomotor and SERVOPACK in one of the specified combinations.Failure t

Pagina 3 - About this Manual

4.3 Basic Functions Settings4-154Operation(2) Stopping Method for Servomotor When an Alarm OccursThere are two types of alarms (Gr.1 and Gr.2) that d

Pagina 4

4 Operation4.3.6 Instantaneous Power Interruption Settings4-164.3.6 Instantaneous Power Interruption SettingsDetermines whether to continue operatio

Pagina 5 -  Trademarks

4.3 Basic Functions Settings4-174Operation4.3.7 SEMI F47 Function (Torque Limit Function for Low DC Power Supply Voltage for Main Circuit)The torque

Pagina 6 - MANDATORY

4 Operation4.3.7 SEMI F47 Function (Torque Limit Function for Low DC Power Supply Voltage for Main Circuit)4-18(1) Execution MethodThis function can

Pagina 7 - Safety Precautions

4.3 Basic Functions Settings4-194Operation(2) Related Parameters∗ The setting unit is a percentage of the rated torque.Note: When using SEMI F47 func

Pagina 8

4 Operation4.3.8 Setting Motor Overload Detection Level4-204.3.8 Setting Motor Overload Detection LevelIn this SERVOPACK, the detection timing of th

Pagina 9

4.3 Basic Functions Settings4-214Operation(2) Changing Detection Timing of Overload (Low Load) Alarm (A.720)An overload (low load) alarm (A.720) can

Pagina 10 - CAUTION

4 Operation4.4.1 Inspection and Checking before Trial Operation4-224.4 Trial OperationThis section describes a trial operation using MECHATROLINK-II

Pagina 11 -  General Precautions

4.4 Trial Operation4-234Operation4.4.2 Trial Operation via MECHATROLINK-IIIThe following table provides the procedures for trial operation via MECHAT

Pagina 12 - Warranty

4 Operation4.4.3 Electronic Gear4-244.4.3 Electronic GearThe electronic gear enables the workpiece travel distance per reference unit input from the

Pagina 13 - (4) Specifications Change

xi General PrecautionsObserve the following general precautions to ensure safe application.• The products shown in illustrations in this manual are s

Pagina 14 - Harmonized Standards

4.4 Trial Operation4-254Operation Encoder ResolutionEncoder resolution can be checked with servomotor model designation.(2) Electronic Gear Ratio Se

Pagina 15 -  Safe Performance

4 Operation4.4.4 Encoder Output Pulses4-264.4.4 Encoder Output PulsesThe encoder pulse output is a signal that is output from the encoder and proces

Pagina 16 - Contents

4.4 Trial Operation4-274Operation4.4.5 Setting Encoder Output PulseSet the encoder output pulse using the following parameter.Pulses from the encoder

Pagina 17

4 Operation4.5.1 Motor Information4-284.5 Test Without Motor FunctionThe test without a motor is used to check the operation of the host controller

Pagina 18

4.5 Test Without Motor Function4-294Operation Encoder TypeThe encoder information for the motor is set in Pn00C.2. An external encoder with fully-cl

Pagina 19

4 Operation4.5.3 Limitations4-304.5.3 LimitationsThe following functions cannot be used during the test without a motor.• Regeneration and dynamic b

Pagina 20

4.5 Test Without Motor Function4-314Operation4.5.4 Digital Operator Displays during Testing without MotorAn asterisk (∗) is displayed before status d

Pagina 21

4 Operation4.6.1 Internal Torque Limit4-324.6 Limiting TorqueThe SERVOPACK provides the following four methods for limiting output torque to protect

Pagina 22 - 1.2 Part Names

4.6 Limiting Torque4-334Operation4.6.2 External Torque LimitUse this function to limit torque by inputting a signal from the host controller at speci

Pagina 23 - 1.3.1 Ratings

4 Operation4.6.3 Checking Output Torque Limiting during Operation4-34(3) Changes in Output Torque during External Torque LimitingThe following diagr

Pagina 24 - 1.3.1 Ratings

xiiWarranty(1) Details of Warranty Warranty PeriodThe warranty period for a product that was purchased (hereinafter called “delivered product”) i

Pagina 25 - 1.3.2 Basic Specifications

4.7 Absolute Encoders4-354Operation4.7 Absolute EncodersIf using an absolute encoder, a system to detect the absolute position can be designed for us

Pagina 26 - ± 1%): 1.2 ms (Typ)

4 Operation4.7.1 Connecting the Absolute Encoder4-364.7.1 Connecting the Absolute EncoderThe following diagram shows the connection between a servom

Pagina 27

4.7 Absolute Encoders4-374Operation(2) Installing the Battery in the Host Controller∗1. The absolute encoder pin numbers for the connector wiring dep

Pagina 28

4 Operation4.7.2 Absolute Data Request (SENS ON Command)4-384.7.2 Absolute Data Request (SENS ON Command)The Turn Sensor ON command (SENS_ON) must b

Pagina 29 - Dynamic

4.7 Absolute Encoders4-394Operation4.7.3 Battery ReplacementIf the battery voltage drops to approximately 2.7 V or less, an absolute encoder battery

Pagina 30

4 Operation4.7.3 Battery Replacement4-403. Remove the old battery and mount the new JZSP-BA01 battery as shown below.4. Close the battery case cover

Pagina 31

4.7 Absolute Encoders4-414Operation4.7.4 Absolute Encoder Setup and ReinitializationSetting up and reinitialization of the absolute encoder are neces

Pagina 32

4 Operation4.7.5 Absolute Data Reception Sequence4-424.7.5 Absolute Data Reception SequenceThe sequence in which the SERVOPACK receives outputs from

Pagina 33 - Fan 1 Fan 2 Fan 3

4.7 Absolute Encoders4-434Operation(2) Absolute Data Reception Sequence1. Send the Turn Sensor ON (SENS_ON) command from the host controller.2. After

Pagina 34

4 Operation4.7.5 Absolute Data Reception Sequence4-44Final absolute data PM is calculated by following formula.PE=M× R+POPS=MS× R+PS’PM=PE-PSNote: T

Pagina 35 - Fan 1 Fan 2

xiii(3) Suitability for Use1. It is the customer’s responsibility to confirm conformity with any standards, codes, or regulations that apply if the Ya

Pagina 36

4.7 Absolute Encoders4-454Operation(3) Rotational Serial Data Specifications and Initial Incremental Pulses Rotational Serial Data SpecificationsThe

Pagina 37 - F21A SERVOPACK

4 Operation4.7.5 Absolute Data Reception Sequence4-46(4) Transferring Alarm ContentsIf an absolute encoder is used, the contents of alarms detected

Pagina 38 - Servomotor

4.7 Absolute Encoders4-474Operation4.7.6 Multiturn Limit SettingThe multiturn limit setting is used in position control applications for a turntable

Pagina 39 - MECHATROLINK-III

4 Operation4.7.7 Multiturn Limit Disagreement Alarm (A.CC0)4-48Set the value, the desired rotational amount -1, to Pn205.Note: The standard specific

Pagina 40 - Host controller

4.7 Absolute Encoders4-494Operation4.7.8 Absolute Encoder Origin OffsetIf using the absolute encoder, the positions of the encoder and the offset of

Pagina 41

4 Operation4.8.1 Servo Alarm Output Signal (ALM)4-504.8 Other Output SignalsThis section explains other output signals.Use these signals according t

Pagina 42 - (1) SERVOPACK Inspection

4.8 Other Output Signals4-514Operation4.8.3 Rotation Detection Output Signal (/TGON)This output signal indicates that the servomotor is rotating at t

Pagina 43 - Operation of Digital Operator

4 Operation4.8.5 Speed Coincidence Output Signal (/V-CMP)4-524.8.5 Speed Coincidence Output Signal (/V-CMP)The speed coincidence output signal (/V-C

Pagina 44 - 2.1 Panel Display

4.8 Other Output Signals4-534Operation4.8.6 Positioning Completed Output Signal (/COIN)This signal indicates that servomotor movement has been comple

Pagina 45 - 2.3 Utility Functions (Fn)

4 Operation4.8.7 Positioning Near Output Signal (/NEAR)4-544.8.7 Positioning Near Output Signal (/NEAR)Before confirming that the positioning comple

Pagina 46 - 2.4 Parameters (Pn)

xivHarmonized Standards North American Safety Standards (UL) European DirectivesModelUL Standards(UL File No.)SERVOPACK SGDV UL508C (E147823)Ser

Pagina 47 - 2.4.3 Setting Parameters

4.8 Other Output Signals4-554Operation4.8.8 Speed Limit Detection Signal (/VLT)This function limits the speed of the servomotor to protect the machin

Pagina 48 - 2.4.3 Setting Parameters

4 Operation4.8.8 Speed Limit Detection Signal (/VLT)4-56 Internal Speed Limit FunctionIf the internal speed limit function is selected in Pn002.1,

Pagina 49 - 2.5 Monitor Displays (Un)

4.9 Safety Function4-574Operation4.9 Safety FunctionThe safety function is incorporated in the SERVOPACK to reduce the risk associated with the machi

Pagina 50 - Wiring and Connection

4 Operation4.9.1 Hard Wire Base Block (HWBB) Function4-58(1) Risk AssessmentWhen using the HWBB function, be sure to perform a risk assessment of th

Pagina 51 - : Main circuit terminals

4.9 Safety Function4-594Operation(3) Resetting the HWBB StateUsually after the servo OFF command (SV_OFF: 32H) is received and the servomotor power i

Pagina 52 - (1) Wire Types

4 Operation4.9.1 Hard Wire Base Block (HWBB) Function4-60(4) Related CommandsIf the HWBB function is working with the /HWBB1 or /HWBB2 signal turned

Pagina 53 - (2) Main Circuit Wires

4.9 Safety Function4-614Operation(6) Connection Example and Specifications of Input Signals (HWBB Signals)The input signals must be redundant. A conn

Pagina 54 - (For servo

4 Operation4.9.1 Hard Wire Base Block (HWBB) Function4-62(7) Operation with Utility FunctionsThe HWBB function works while the SERVOPACK operates in

Pagina 55 - 3 Wiring and Connection

4.9 Safety Function4-634Operation(10) Dynamic BrakeIf the dynamic brake is enabled in Pn001.0 (Stopping Method for Servomotor after SV_OFF Command is

Pagina 56

4 Operation4.9.2 External Device Monitor (EDM1)4-64(1) Connection Example and Specifications of EDM1 Output SignalConnection example and specificati

Pagina 57

xv Safety Standards Safe PerformanceModel Safety Standards StandardsSERVOPACK SGDVSafety of MachineryEN ISO13849-1: 2008EN 954-1 IEC 60204-1Function

Pagina 58 - 3.1 Main Circuit Wiring

4.9 Safety Function4-654Operation4.9.3 Application Example of Safety FunctionsAn example of using safety functions is shown below. (1) Connection Exa

Pagina 59

4 Operation4.9.4 Confirming Safety Functions4-66(3) Procedure4.9.4 Confirming Safety FunctionsWhen starting the equipment or replacing the SERVOPACK

Pagina 60

4.9 Safety Function4-674Operation4.9.5 Connecting a Safety Function DeviceThere are two types of the safety function’s jumper connectors that are att

Pagina 61

4 Operation4.9.5 Connecting a Safety Function Device4-683. Connect the safety function device to the safety connector (CN8).Note: If you do not conn

Pagina 62

4-694Operation4.9.6 Precautions for Safety Functions WARNING• To check that the HWBB function satisfies the safety requirements of the system, be sure

Pagina 63

5-15Adjustments5Adjustments5.1 Type of Adjustments and Basic Adjustment Procedure . . . . . . . . . . . . . .5-35.1.1 Adjustments . . . . . . .

Pagina 64 -  400-V SERVOPACK SGDV-D

5 Adjustments 5-25.8 Additional Adjustment Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-545.8.1 Switching Gain Settin

Pagina 65 - (2) Precautions

5.1 Type of Adjustments and Basic Adjustment Procedure5-35Adjustments5.1 Type of Adjustments and Basic Adjustment ProcedureThis section describes typ

Pagina 66

5 Adjustments5.1.2 Basic Adjustment Procedure5-45.1.2 Basic Adjustment ProcedureThe basic adjustment procedure is shown in the following flowchart.

Pagina 67 - 3.2 I/O Signal Connections

5.1 Type of Adjustments and Basic Adjustment Procedure5-55Adjustments5.1.3 Monitoring Operation during AdjustmentCheck the operating status of the ma

Pagina 68 - (2) Output Signals

xviContentsAbout this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iiiS

Pagina 69

5 Adjustments5.1.3 Monitoring Operation during Adjustment5-6The following signals can be monitored by selecting functions with parameters Pn006 and

Pagina 70 - 3.3 I/O Signal Allocations

5.1 Type of Adjustments and Basic Adjustment Procedure5-75Adjustments<Example>Analog monitor output at n.00 (motor rotating speed setting)(4)

Pagina 71

5 Adjustments5.1.4 Safety Precautions on Adjustment of Servo Gains5-85.1.4 Safety Precautions on Adjustment of Servo GainsSet the following protecti

Pagina 72 - 3.3 I/O Signal Allocations

5.1 Type of Adjustments and Basic Adjustment Procedure5-95AdjustmentsUnder these conditions, the following equation is used to calculate the maximum

Pagina 73 - 3.4.1 Sequence Input Circuit

5 Adjustments5.1.4 Safety Precautions on Adjustment of Servo Gains5-10 Related AlarmsWhen an alarm occurs, refer to 9 Troubleshooting and take the

Pagina 74 - 5 to 12 VDC

5.2 Tuning-less Function5-115Adjustments5.2 Tuning-less FunctionThe tuning-less function is enabled in the factory settings. If resonance is generate

Pagina 75 - (3) Safety Output Circuit

5 Adjustments5.2.1 Tuning-less Function5-12∗ Operate using SigmaWin+.(3) Automatically Setting the Notch FilterUsually, set this function to Auto Se

Pagina 76

5.2 Tuning-less Function5-135Adjustments Load Levela) Using the utility functionTo change the setting, refer to 5.2.2 Tuning-less Levels Setting (F

Pagina 77 - 3.6 Encoder Connection

5 Adjustments5.2.2 Tuning-less Levels Setting (Fn200) Procedure5-145.2.2 Tuning-less Levels Setting (Fn200) ProcedureThe procedure to use the tuning

Pagina 78 - (2) Absolute Encoder

5.2 Tuning-less Function5-155AdjustmentsNote: If the rigidity level is changed, the automatically set notch filter will be canceled. If vibration occ

Pagina 79

xviiChapter 3 Wiring and Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-13.1 Main Circuit Wiring. . . . . . . . . . . .

Pagina 80 - JUSP-RA-E

5 Adjustments5.2.3 Related Parameters5-16(5) Tuning-less Function TypeThe following table shows the types of tuning-less functions for the version o

Pagina 81

5.3 Advanced Autotuning (Fn201)5-175Adjustments5.3 Advanced Autotuning (Fn201)This section describes the adjustment using advanced autotuning.5.3.1 A

Pagina 82

5 Adjustments5.3.1 Advanced Autotuning5-18• Moment of inertia ratio• Gains (e.g., position loop gain and speed loop gain)• Filters (torque reference

Pagina 83 - Signal generation

5.3 Advanced Autotuning (Fn201)5-195AdjustmentsNote:If a setting is made for calculating the moment of inertia, the mode switch function will be disa

Pagina 84

5 Adjustments5.3.2 Advanced Autotuning Procedure 5-205.3.2 Advanced Autotuning Procedure The following procedure is used for advanced autotuning.Adv

Pagina 85

5.3 Advanced Autotuning (Fn201)5-215Adjustments3-4STROKE (Travel Distance) SettingTravel distance setting range:The travel distance setting range is

Pagina 86 - Operation

5 Adjustments5.3.2 Advanced Autotuning Procedure 5-22(2) Failure in Operation When "NO-OP" Flashes on the Display8Gain AdjustmentWhen th

Pagina 87

5.3 Advanced Autotuning (Fn201)5-235Adjustments When "Error" Flashes on the Display When an Error Occurs during Calculation of Moment of

Pagina 88

5 Adjustments5.3.2 Advanced Autotuning Procedure 5-24(3) Related Functions on Advanced AutotuningThis section describes functions related to advanc

Pagina 89 - 4.3 Basic Functions Settings

5.3 Advanced Autotuning (Fn201)5-255Adjustments Friction CompensationThis function compensates for changes in the following conditions.• Changes in

Pagina 90

xviii4.6 Limiting Torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-324.6.1 Internal Torque

Pagina 91

5 Adjustments5.3.3 Related Parameters5-265.3.3 Related ParametersThe following table lists parameters related to this function and their possibility

Pagina 92

5.4 Advanced Autotuning by Reference (Fn202)5-275Adjustments5.4 Advanced Autotuning by Reference (Fn202)Adjustments with advanced autotuning by refer

Pagina 93 - 4.3.3 Software Limit Settings

5 Adjustments5.4.1 Advanced Autotuning by Reference5-28(1) PreparationCheck the following settings before performing advanced autotuning by referenc

Pagina 94 - 4.3.4 Holding Brakes

5.4 Advanced Autotuning by Reference (Fn202)5-295Adjustments5.4.2 Advanced Autotuning by Reference Procedure The following procedure is used for adva

Pagina 95

5 Adjustments5.4.2 Advanced Autotuning by Reference Procedure 5-30(2) Failure in Operation When "NO-OP" Flashes on the Display When &quo

Pagina 96 - Photocoupler

5.4 Advanced Autotuning by Reference (Fn202)5-315Adjustments(3) Related Functions on Advanced Autotuning by ReferenceThis section describes functions

Pagina 97 - 4.3.4 Holding Brakes

5 Adjustments5.4.2 Advanced Autotuning by Reference Procedure 5-32 Friction CompensationThis function compensates for changes in the following cond

Pagina 98

5.4 Advanced Autotuning by Reference (Fn202)5-335Adjustments5.4.3 Related ParametersThe following table lists parameters related to this function and

Pagina 99

5 Adjustments5.5.1 One-parameter Tuning5-345.5 One-parameter Tuning (Fn203)Adjustments with one-parameter tuning are described below.5.5.1 One-param

Pagina 100 - 4.3 Basic Functions Settings

5.5 One-parameter Tuning (Fn203)5-355Adjustments5.5.2 One-parameter Tuning ProcedureThe following procedure is used for one-parameter tuning.There ar

Pagina 101 - 4 Operation

xix5.7 Vibration Suppression Function (Fn205) . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-495.7.1 Vibration Suppression Function . . . .

Pagina 102

5 Adjustments5.5.2 One-parameter Tuning Procedure5-364-2Type SelectionSelect the type according to the machine element to be driven. If there is no

Pagina 103 - Rotation

5.5 One-parameter Tuning (Fn203)5-375Adjustments Setting the Tuning Mode 2 or 3Step Display after Operation Keys Operation1Press the Key to view t

Pagina 104 - (2) Related Parameters

5 Adjustments5.5.2 One-parameter Tuning Procedure5-388If readjustment is required, select the digit with the or Key or change the FF LEVEL and FB

Pagina 105

5.5 One-parameter Tuning (Fn203)5-395Adjustments(2) Related Functions on One-parameter TuningThis section describes functions related to one-paramete

Pagina 106

5 Adjustments5.5.2 One-parameter Tuning Procedure5-40 Friction CompensationThis function compensates for changes in the following conditions.• Chan

Pagina 107 - 4.4 Trial Operation

5.5 One-parameter Tuning (Fn203)5-415Adjustments5.5.3 One-parameter Tuning ExampleThe following procedure is used for one-parameter tuning on the con

Pagina 108 - 4.4 Trial Operation

5 Adjustments5.5.4 Related Parameters5-425.5.4 Related ParametersThe following table lists parameters related to this function and their possibility

Pagina 109 - 4.4.3 Electronic Gear

5.6 Anti-Resonance Control Adjustment Function (Fn204)5-435Adjustments5.6 Anti-Resonance Control Adjustment Function (Fn204)This section describes th

Pagina 110

5 Adjustments5.6.2 Anti-Resonance Control Adjustment Function Operating Procedure5-445.6.2 Anti-Resonance Control Adjustment Function Operating Proc

Pagina 111 - 4.4.4 Encoder Output Pulses

5.6 Anti-Resonance Control Adjustment Function (Fn204)5-455Adjustments6Press the Key. The cursor will move to "damp," and the flashing of

Pagina 112

Copyright © 2008 YASKAWA ELECTRIC CORPORATIONAll rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or tra

Pagina 113 - 4.5.1 Motor Information

xx7.4 Monitoring Output Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-67.4.1 Interpreting Output Sign

Pagina 114 -  Encoder Type

5 Adjustments5.6.2 Anti-Resonance Control Adjustment Function Operating Procedure5-46 With Determined Vibration FrequencyStep Display after Operati

Pagina 115 - 4.5.3 Limitations

5.6 Anti-Resonance Control Adjustment Function (Fn204)5-475Adjustments(2) For Fine-tuning After Adjusting the Anti-Resonance Control7Select the digit

Pagina 116

5 Adjustments5.6.3 Related Parameters5-485.6.3 Related ParametersThe following table lists parameters related to this function and their possibility

Pagina 117 - 4.6 Limiting Torque

5.7 Vibration Suppression Function (Fn205)5-495Adjustments5.7 Vibration Suppression Function (Fn205)The vibration suppression function is described i

Pagina 118 - 4.6.2 External Torque Limit

5 Adjustments5.7.2 Vibration Suppression Function Operating Procedure5-50Note: As a guideline, change the setting 10% at a time. The smaller the set

Pagina 119

5.7 Vibration Suppression Function (Fn205)5-515Adjustments(2) Operating ProcedureStep Display after Operation Keys Operation1 Input a operation refer

Pagina 120 - PROHIBITED

5 Adjustments5.7.2 Vibration Suppression Function Operating Procedure5-52(3) Related Function on Vibration Suppression FunctionThis section describe

Pagina 121 - SERVOPACK

5.7 Vibration Suppression Function (Fn205)5-535Adjustments5.7.3 Related ParametersThe following table lists parameters related to this function and t

Pagina 122 - 46 and 64

5 Adjustments5.8.1 Switching Gain Settings5-545.8 Additional Adjustment FunctionThis section describes the functions that can be used for additional

Pagina 123

5.8 Additional Adjustment Function5-555Adjustments(2) Manual Gain SwitchingManual gain switching uses G-SEL of the servo command output signals (SVCM

Pagina 124 - 4.7.3 Battery Replacement

1-11Outline1Outline1.1 Σ-V Series SERVOPACKs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-21.2 Part Names . . . . . .

Pagina 125

5 Adjustments5.8.1 Switching Gain Settings5-56 Relationship between the Waiting and Switching Times for Gain SwitchingIn this example, the "po

Pagina 126

5.8 Additional Adjustment Function5-575Adjustments(5) Parameters for Automatic Gain Switching(6) Related MonitorNote: When using the tuning-less func

Pagina 127 - (1) Outline of Absolute Data

5 Adjustments5.8.2 Manual Adjustment of Friction Compensation5-585.8.2 Manual Adjustment of Friction CompensationFriction compensation rectifies the

Pagina 128 - 4.7 Absolute Encoders

5.8 Additional Adjustment Function5-595Adjustments(2) Operating Procedure for Friction CompensationThe following procedure is used for friction compe

Pagina 129

5 Adjustments5.8.3 Current Control Mode Selection Function5-605.8.3 Current Control Mode Selection FunctionThis function reduces high-frequency nois

Pagina 130

5.8 Additional Adjustment Function5-615Adjustments5.8.6 Backlash Compensation Function(1) OverviewWhen driving a machine with backlash, there will be

Pagina 131 - PAO Output

5 Adjustments5.8.6 Backlash Compensation Function5-62 Backlash Compensation Time ConstantSet a time constant for a first order lag filter to use wh

Pagina 132 - 4.7.6 Multiturn Limit Setting

5.8 Additional Adjustment Function5-635Adjustments When Servo is ONThe backlash compensation value (Pn231) is added in the compensation direction wh

Pagina 133 - Rotational

5 Adjustments5.8.6 Backlash Compensation Function5-64 When Servo is OFFBacklash compensation is not applied when the servo is OFF (i.e., when the s

Pagina 134

5.8 Additional Adjustment Function5-655Adjustments(5) Monitor Functions (Un Monitoring)(6) MECHATROLINK Monitor InformationThis section describes the

Pagina 135 - 4.8 Other Output Signals

1 Outline 1-21.1 Σ-V Series SERVOPACKsThe Σ-V Series SERVOPACKs are designed for applications that require frequent high-speed, high-pre-cision posi

Pagina 136 - (2) Related Parameter

5 Adjustments5.8.6 Backlash Compensation Function5-66 Related Monitoring DiagramsParameters Monitor Information Output Unit RemarksPn824Pn8250003H

Pagina 137 - /V-CMP is output in

5.9 Compatible Adjustment Function5-675Adjustments5.9 Compatible Adjustment FunctionThe Σ-V series SERVOPACKs have adjustment functions as explained

Pagina 138 - Position error

5 Adjustments5.9.2 Mode Switch (P/PI Switching)5-685.9.2 Mode Switch (P/PI Switching)The mode switch automatically switches between proportional and

Pagina 139

5.9 Compatible Adjustment Function5-695Adjustments(2) Operating Examples for Different Switching Conditions Using the Torque Reference [Factory Sett

Pagina 140 - (2) Speed Limit Setting

5 Adjustments5.9.3 Torque Reference Filter5-705.9.3 Torque Reference FilterAs shown in the following diagram, the torque reference filter contains f

Pagina 141

5.9 Compatible Adjustment Function5-715Adjustments(2) Notch FilterThe notch filter can eliminate specific frequency elements generated by the vibrati

Pagina 142 - 4.9 Safety Function

5 Adjustments5.9.4 Position Integral5-725.9.4 Position IntegralThe position integral is the integral function of the position loop. It is used for t

Pagina 143 - (1) Risk Assessment

6-16Utility Functions (Fn)6Utility Functions (Fn)6.1 List of Utility Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 144 - (3) Resetting the HWBB State

6 Utility Functions (Fn) 6-26.1 List of Utility FunctionsUtility functions are used to execute the functions related to servomotor operation and

Pagina 145

6.2 Alarm History Display (Fn000)6-36Utility Functions (Fn)6.2 Alarm History Display (Fn000)This function displays the last ten alarms that have o

Pagina 146 -  Specifications

1.3 SERVOPACK Ratings and Specifications1-31Outline1.3 SERVOPACK Ratings and SpecificationsThis section describes the ratings and specifications of S

Pagina 147

6 Utility Functions (Fn) 6-46.3 JOG Operation (Fn002)JOG operation is used to check the operation of the servomotor under speed control without c

Pagina 148 - WARNING

6.3 JOG Operation (Fn002)6-56Utility Functions (Fn)6Press the Key.The status display changes from "BB" to "RUN", and the serv

Pagina 149

6 Utility Functions (Fn) 6-66.4 Origin Search (Fn003)The origin search is designed to position the origin pulse position of the incremental encod

Pagina 150 - (2) Failure Detection Method

6.4 Origin Search (Fn003)6-76Utility Functions (Fn)(2) Operating ProcedureUse the following procedure.Step Display after Operation Keys Operation1

Pagina 151 - (3) Procedure

6 Utility Functions (Fn) 6-86.5 Program JOG Operation (Fn004)The program JOG operation is a utility function, that allows continuous operation de

Pagina 152 - (1) Connector Type A

6.5 Program JOG Operation (Fn004)6-96Utility Functions (Fn)Note: When Pn536 (Number of Times of Program JOG Movement) is set to 0, infinite time o

Pagina 153 - Safety function’s

6 Utility Functions (Fn) 6-10Note: When Pn536 (number of times of program JOG movement) is set to 0, infinite time operation is enabled. To stop

Pagina 154

6.5 Program JOG Operation (Fn004)6-116Utility Functions (Fn)∗ When using an SGMCS direct drive motor, the setting unit will be automatically chang

Pagina 155 - Adjustments

6 Utility Functions (Fn) 6-12∗ The settings can be changed for a parameter.6When the set program JOG operation movement is completed, "END&q

Pagina 156 - 5 Adjustments

6.6 Initializing Parameter Settings (Fn005)6-136Utility Functions (Fn)6.6 Initializing Parameter Settings (Fn005)This function is used when return

Pagina 157 - 5.1.1 Adjustments

1 Outline1.3.1 Ratings1-4(4) SGDV with Three-phase, 400-V Rating∗ Refer to 3.7 Connecting Regenerative Resistors for details.SGDV (Three Phase, 400

Pagina 158

6 Utility Functions (Fn) 6-146.7 Clearing Alarm History (Fn006)The clear alarm history function deletes all of the alarm history recorded in the

Pagina 159

6.8 Offset Adjustment of Analog Monitor Output (Fn00C)6-156Utility Functions (Fn)6.8 Offset Adjustment of Analog Monitor Output (Fn00C)This functi

Pagina 160 - (3) Setting Monitor Factor

6 Utility Functions (Fn) 6-16(3) Operating ProcedureUse the following procedure to perform the offset adjustment of analog monitor output.Step Di

Pagina 161 - (4) Related Parameters

6.9 Gain Adjustment of Analog Monitor Output (Fn00D)6-176Utility Functions (Fn)6.9 Gain Adjustment of Analog Monitor Output (Fn00D)This function i

Pagina 162

6 Utility Functions (Fn) 6-18(3) Operating ProcedureUse the following procedure to perform the gain adjustment of analog monitor output.Step Disp

Pagina 163 -  Related Parameters

6.10 Automatic Offset-Signal Adjustment of the Motor Current Detection Signal (Fn00E)6-196Utility Functions (Fn)6.10 Automatic Offset-Signal Adjus

Pagina 164 -  Related Alarms

6 Utility Functions (Fn) 6-206.11 Manual Offset-Signal Adjustment of the Motor Current Detection Signal (Fn00F)Use this function only if the torq

Pagina 165 - 5.2.1 Tuning-less Function

6.11 Manual Offset-Signal Adjustment of the Motor Current Detection Signal (Fn00F)6-216Utility Functions (Fn)Repeat the operations of steps 4 to 6

Pagina 166 -  Rigidity Level

6 Utility Functions (Fn) 6-226.12 Write Prohibited Setting (Fn010)This function prevents changing parameters by mistake and sets restrictions on

Pagina 167 -  Load Level

6.12 Write Prohibited Setting (Fn010)6-236Utility Functions (Fn)(1) PreparationThere are no tasks that must be performed before the execution.(2)

Pagina 168

1.3 SERVOPACK Ratings and Specifications1-51Outline1.3.2 Basic SpecificationsBasic specifications of SERVOPACKs are shown below.Drive Method Sine-wav

Pagina 169 -  Resonance Sound

6 Utility Functions (Fn) 6-246.13 Servomotor Model Display (Fn011)This function is used to check the servomotor model, voltage, capacity, encoder

Pagina 170 - 5.2.3 Related Parameters

6.14 Software Version Display (Fn012)6-256Utility Functions (Fn)6.14 Software Version Display (Fn012)Select Fn012 to check the SERVOPACK and encod

Pagina 171 - 5.3.1 Advanced Autotuning

6 Utility Functions (Fn) 6-266.15 Resetting Configuration Errors in Option Modules (Fn014)The SERVOPACK with option module recognizes installatio

Pagina 172

6.16 Vibration Detection Level Initialization (Fn01B)6-276Utility Functions (Fn)6.16 Vibration Detection Level Initialization (Fn01B)This function

Pagina 173 -  When Using a 13-bit Encoder

6 Utility Functions (Fn) 6-28(2) Operating ProcedureUse the following procedure.(3) Related ParametersThe following table lists parameters relate

Pagina 174

6.17 Display of SERVOPACK and Servomotor ID (Fn01E)6-296Utility Functions (Fn)6.17 Display of SERVOPACK and Servomotor ID (Fn01E)This function dis

Pagina 175

6 Utility Functions (Fn) 6-30(2) Operating ProcedureUse the following procedure.Step Display after Operation Keys Operation1Press the Key to vi

Pagina 176 - (2) Failure in Operation

6.18 Display of Servomotor ID in Feedback Option Module (Fn01F)6-316Utility Functions (Fn)6.18 Display of Servomotor ID in Feedback Option Module

Pagina 177

6 Utility Functions (Fn) 6-32(2) Operating ProcedureUse the following procedure.∗ When fully-closed loop control is being used, step 2 is not inc

Pagina 178 -  Vibration Suppression

6.19 Origin Setting (Fn020)6-336Utility Functions (Fn)6.19 Origin Setting (Fn020)When using an external absolute encoder for fully-closed loop con

Pagina 179 -  Feedforward

1 Outline1.3.2 Basic Specifications1-6I/OSignalsEncoder Output PulsePhase A, B, C: line driver Encoder output pulse: any setting ratio (Refer to 4.4

Pagina 180 - 5.3.3 Related Parameters

6 Utility Functions (Fn) 6-346.20 Software Reset (Fn030)This function enables resetting the SERVOPACK internally from software. This function is

Pagina 181

6.21 EasyFFT (Fn206)6-356Utility Functions (Fn)6.21 EasyFFT (Fn206)EasyFFT sends a frequency waveform reference from the SERVOPACK to the servomot

Pagina 182 - (1) Preparation

6 Utility Functions (Fn) 6-36(2) Operating ProcedureUse the following procedure.Step Display after Operation Keys Operation1Press the Key to vi

Pagina 183

6.21 EasyFFT (Fn206)6-376Utility Functions (Fn)6When the detection processing is successfully com-pleted, "Measure" stops flashing and t

Pagina 184

6 Utility Functions (Fn) 6-38(3) Related ParametersThe following table lists parameters related to this function and their possibility of being c

Pagina 185

6.22 Online Vibration Monitor (Fn207)6-396Utility Functions (Fn)6.22 Online Vibration Monitor (Fn207)If vibration is generated during operation an

Pagina 186

6 Utility Functions (Fn) 6-40(2) Operating Procedure Use the following procedure.Step Display after Operation Keys Operation1Press the Key to v

Pagina 187 - 5.4.3 Related Parameters

6.22 Online Vibration Monitor (Fn207)6-416Utility Functions (Fn)(3) Related ParametersThe following table lists parameters related to this functio

Pagina 188 - 5.5.1 One-parameter Tuning

7-17Monitor Displays (Un)7Monitor Displays (Un)7.1 List of Monitor Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 189

7 Monitor Displays (Un) 7-27.1 List of Monitor DisplaysThe monitor displays can be used for monitoring the I/O signal status, and SERVOPACK inter

Pagina 190

1.3 SERVOPACK Ratings and Specifications1-71Outline∗1. Speed regulation by load regulation is defined as follows:∗2. Refer to 1.3.1 Ratings for detai

Pagina 191 - Status Display

7.2 Viewing Monitor Displays7-37Monitor Displays (Un)7.2 Viewing Monitor DisplaysThe monitor display can be checked or viewed in the Parameter/Mon

Pagina 192

7 Monitor Displays (Un)7.3.1 Interpreting Input Signal Display Status7-47.3 Monitoring Input SignalsThe status of input signals can be checked wi

Pagina 193

7.3 Monitoring Input Signals7-57Monitor Displays (Un)7.3.2 Input Signal Display ExampleInput signals are displayed as shown below.• When the /DEC

Pagina 194

7 Monitor Displays (Un)7.4.1 Interpreting Output Signal Display Status7-67.4 Monitoring Output SignalsThe status of output signals can be checked

Pagina 195 - Positioning completed signal

7.5 Monitoring Safety Input Signals7-77Monitor Displays (Un)7.5 Monitoring Safety Input SignalsThe status of safety input signals can be checked w

Pagina 196 - 5.5.4 Related Parameters

8-18Fully-closed Loop Control8Fully-closed Loop Control8.1 System Configuration and Connection Example for SERVOPACK with Fully-closed Loop Control

Pagina 197

8 Fully-closed Loop Control8.1.1 System Configuration8-28.1 System Configuration and Connection Example for SERVOPACK with Fully-closed Loop Control

Pagina 198

8.1 System Configuration and Connection Example for SERVOPACK with Fully-closed Loop Control8-38Fully-closed Loop Control8.1.2 Internal Block Diagram

Pagina 199

8 Fully-closed Loop Control8.1.3 Serial Converter Unit8-48.1.3 Serial Converter UnitThis section provides the specification of the serial converter

Pagina 200

8.1 System Configuration and Connection Example for SERVOPACK with Fully-closed Loop Control8-58Fully-closed Loop Control(2) Analog Signal Input Timi

Pagina 201

1 Outline1.3.3 MECHATROLINK-III Function Specifications1-81.3.3 MECHATROLINK-III Function SpecificationsThe following table shows the specifications

Pagina 202 - 5.6.3 Related Parameters

8 Fully-closed Loop Control8.1.4 Example of Connections to External Encoders8-68.1.4 Example of Connections to External Encoders(1) External Encoder

Pagina 203

8.1 System Configuration and Connection Example for SERVOPACK with Fully-closed Loop Control8-78Fully-closed Loop Control8.1.5 Encoder Output Pulse S

Pagina 204 - (1) Operating Flow

8 Fully-closed Loop Control8.1.6 Precautions When Using an External Incremental Encoder by Magnescale8-88.1.6 Precautions When Using an External Inc

Pagina 205 - (2) Operating Procedure

8.1 System Configuration and Connection Example for SERVOPACK with Fully-closed Loop Control8-98Fully-closed Loop Control When Passing 1st Zero Poin

Pagina 206

8 Fully-closed Loop Control8.1.6 Precautions When Using an External Incremental Encoder by Magnescale8-10 When Using an External Encoder with Multi

Pagina 207 - 5.7.3 Related Parameters

8.2 SERVOPACK Startup Procedure8-118Fully-closed Loop Control8.2 SERVOPACK Startup ProcedureFirst check that the SERVOPACK operates correctly with se

Pagina 208 - 5.8.1 Switching Gain Settings

8 Fully-closed Loop Control8-124Perform a program JOG opera-tion.Items to Check• Does the fully-closed loop control operate correctly when operating

Pagina 209 - (3) Automatic Gain Switching

8.3 Parameter Settings for Fully-closed Loop Control8-138Fully-closed Loop Control8.3 Parameter Settings for Fully-closed Loop ControlThis section de

Pagina 210

8 Fully-closed Loop Control8.3.1 Motor Rotation Direction8-148.3.1 Motor Rotation DirectionThe motor rotation direction can be set. To perform fully

Pagina 211 - (6) Related Monitor

8.3 Parameter Settings for Fully-closed Loop Control8-158Fully-closed Loop Control(3) Relation between Motor Rotation Direction and External Encoder

Pagina 212

1.4 SERVOPACK Internal Block Diagrams1-91Outline1.4 SERVOPACK Internal Block Diagrams1.4.1 Single-phase 100 V, SGDV-R70F21A, -R90F21A, -2R1F21A Model

Pagina 213

8 Fully-closed Loop Control8.3.2 Sine Wave Pitch (Frequency) for an External Encoder8-168.3.2 Sine Wave Pitch (Frequency) for an External EncoderSet

Pagina 214 - Position

8.3 Parameter Settings for Fully-closed Loop Control8-178Fully-closed Loop Control(2) Related ParameterNote: The maximum setting for the encoder outp

Pagina 215 - (1) Overview

8 Fully-closed Loop Control8.3.4 External Absolute Encoder Data Reception Sequence8-18(2) Absolute Data Transmission Sequence and Contents1. Send th

Pagina 216

8.3 Parameter Settings for Fully-closed Loop Control8-198Fully-closed Loop Control(3) Serial Data SpecificationsThe serial data is output from the PA

Pagina 217

8 Fully-closed Loop Control8.3.5 Electronic Gear8-208.3.5 Electronic GearRefer to 4.4.3 Electronic Gear for the purpose of setting the electronic ge

Pagina 218

8.3 Parameter Settings for Fully-closed Loop Control8-218Fully-closed Loop Control Setting ExampleIf the servomotor moves 0.2 μm for every pulse of

Pagina 219

8 Fully-closed Loop Control8.3.7 Analog Monitor Signal8-228.3.7 Analog Monitor SignalThe position error between servomotor and load can be monitored

Pagina 220

9-19Troubleshooting9Troubleshooting9.1 Alarm Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-29

Pagina 221 - 5.9.1 Feedforward Reference

9 Troubleshooting9.1.1 List of Alarms9-29.1 Alarm DisplaysThe following sections describe troubleshooting in response to alarm displays.The alarm na

Pagina 222 - (1) Related Parameters

9.1 Alarm Displays9-39TroubleshootingA.320 Regenerative OverloadRegenerative energy exceeds regenerative resistor capacity.Gr.2 AvailableA.330Main Ci

Pagina 223

iiiAbout this ManualThis manual describes information required for designing, testing, adjusting, and maintaining Σ-V Series SERVOPACKs.Keep this manu

Pagina 224 - 5.9.3 Torque Reference Filter

1 Outline1.4.3 Single-phase 200 V, SGDV-120A21A008000 Model1-101.4.3 Single-phase 200 V, SGDV-120A21A008000 Model1.4.4 Three-phase 200 V, SGDV-R70A2

Pagina 225 - (2) Notch Filter

9 Troubleshooting9.1.1 List of Alarms9-4A.b33 Current Detection Error 3 The detection circuit for the current is faulty. Gr.1 N/AA.b6AMECHATROLINK C

Pagina 226 - 5.9.4 Position Integral

9.1 Alarm Displays9-59TroubleshootingA.E02MECHATROLINK Internal Synchronization Error 1Synchronization error during MECHATROLINK communications with

Pagina 227 - Utility Functions (Fn)

9 Troubleshooting9.1.1 List of Alarms9-6A.F50Servomotor Main Circuit Cable DisconnectionThe servomotor did not operate or power was not supplied to

Pagina 228 - 6.1 List of Utility Functions

9.1 Alarm Displays9-79Troubleshooting9.1.2 Troubleshooting of AlarmsIf an error occurs in servo drives, an alarm display such as A. and CPF will

Pagina 229

9 Troubleshooting9.1.2 Troubleshooting of Alarms9-8A.041:Encoder Output Pulse Setting ErrorThe encoder output pulse (Pn212) is out of the setting ra

Pagina 230 - 6.3 JOG Operation (Fn002)

9.1 Alarm Displays9-99TroubleshootingA.100:Overcurrent or Heat Sink Overheated(An overcurrent flowed through the IGBT or heat sink of SERVO-PACK over

Pagina 231 - 6.3 JOG Operation (Fn002)

9 Troubleshooting9.1.2 Troubleshooting of Alarms9-10A.300:Regeneration Error• Regenerative resistor capacity (Pn600) is set to a value other than 0

Pagina 232 - 6.4 Origin Search (Fn003)

9.1 Alarm Displays9-119TroubleshootingA.330:Main Circuit Power Supply Wiring Error(Detected when the power to the main circuit is turned ON.)The rege

Pagina 233

9 Troubleshooting9.1.2 Troubleshooting of Alarms9-12A.410:Undervoltage(Detected in the SER-VOPACK main circuit power supply section.)• For 100-VAC S

Pagina 234 - (2) Additional Information

9.1 Alarm Displays9-139TroubleshootingA.710:A.720:Overload A.710: High LoadA.720: Low LoadIncorrect wiring or contact fault of servomotor and encoder

Pagina 235

1.4 SERVOPACK Internal Block Diagrams1-111Outline1.4.5 Three-phase 200 V, SGDV-2R8A21 Model∗ The following SERVOPACKs do not have cooling fans: SGDV

Pagina 236

9 Troubleshooting9.1.2 Troubleshooting of Alarms9-14A.810:Encoder Backup Error(Only when an absolute encoder is connected.)(Detected on the encoder

Pagina 237 - (5) Operating Procedure

9.1 Alarm Displays9-159TroubleshootingA.860:Encoder Overheated(Only when an absolute encoder is connected.)(Detected on the encoder side.)The ambient

Pagina 238 - Pn536=00010

9 Troubleshooting9.1.2 Troubleshooting of Alarms9-16A.b6b:MECHATROLINK Communications ASIC Error 2MECHATROLINK data recep-tion error occurred due to

Pagina 239

9.1 Alarm Displays9-179TroubleshootingA.C90:Encoder Communica-tions ErrorContact fault of connector or incorrect wiring for encoder cable.Check the c

Pagina 240

9 Troubleshooting9.1.2 Troubleshooting of Alarms9-18A.Cb0:Encoder Echoback Er-rorThe wiring and contact for encoder cable are incorrect.Check the wi

Pagina 241 - (2) Preparation

9.1 Alarm Displays9-199TroubleshootingA.d00:Position Error Over-flow (Position error exceeded the value set in the excessive position error alarm lev

Pagina 242 - (3) Operating Procedure

9 Troubleshooting9.1.2 Troubleshooting of Alarms9-20A.E42:MECHATROLINK Sta-tion Address Setting ErrorThe station address is out of the allowable set

Pagina 243

9.1 Alarm Displays9-219TroubleshootingA.E63:MECHATROLINK Synchronization Frame Not Received AlarmMECHATROLINK wiring is incorrect.Check the MECHATROL

Pagina 244

9 Troubleshooting9.1.2 Troubleshooting of Alarms9-22A.Eb1:Safety Function Signal Input Timing ErrorThe lag between activations of the input signals

Pagina 245 - Detection Signal (Fn00E)

9.2 Warning Displays9-239Troubleshooting9.2 Warning DisplaysThe following sections describe troubleshooting in response to warning displays.The warni

Pagina 246 - Detection Signal (Fn00F)

1 Outline1.4.7 Three-phase 200 V, SGDV-120A21A Model1-121.4.7 Three-phase 200 V, SGDV-120A21A Model1.4.8 Three-phase 200 V, SGDV-180A21A, -200A21A M

Pagina 247

9 Troubleshooting9.2.1 List of Warnings9-24∗1. Use Pn008.2 to activate or not the warning detection.∗2. Use Pn800.1 to activate or not the warning d

Pagina 248 - 6 Utility Functions (Fn)

9.2 Warning Displays9-259Troubleshooting9.2.2 Troubleshooting of WarningsRefer to the following table to identity the cause of a warning and the acti

Pagina 249

9 Troubleshooting9.2.2 Troubleshooting of Warnings9-26A.920: Regenerative Overload(Warning before the alarm A.320 occurs)The power supply volt-age e

Pagina 250 - Use the following procedure

9.2 Warning Displays9-279TroubleshootingA.94EData Setting Warning 5 (Latch mode error)Latch mode error is detected.Refer to 9.3 Monitoring Communica

Pagina 251

9 Troubleshooting9.2.2 Troubleshooting of Warnings9-28A.962MECHATROLINKCommunicationsWarning(FCS Error)MECHATROLINK wiring is incorrect.Confirm the

Pagina 252

9.2 Warning Displays9-299TroubleshootingA.97ACommand Warn-ing 7(Phase Error)A command that cannot be executed in the cur-rent phase was sent. –Send a

Pagina 253

9 Troubleshooting9-309.3 Monitoring Communication Data on Occurrence of an Alarm or WarningThe command data received on occurrence of an alarm or war

Pagina 254 - (3) Related Parameters

9.4 Troubleshooting Malfunction Based on Operation and Conditions of the Servomotor9-319Troubleshooting9.4 Troubleshooting Malfunction Based on Opera

Pagina 255

9 Troubleshooting9-32Abnormal Noise from ServomotorThe servomotor largely vibrated during execution of tuning-less function.Check the motor speed wav

Pagina 256

9.4 Troubleshooting Malfunction Based on Operation and Conditions of the Servomotor9-339TroubleshootingServomotor Vi-brates at Fre-quency of Approx.

Pagina 257

1.4 SERVOPACK Internal Block Diagrams1-131Outline1.4.9 Three-phase 200 V, SGDV-330A21A Model1.4.10 Three-phase 200 V, SGDV-470A21A, -550A21A ModelsL1

Pagina 258 - Encoder model

9 Troubleshooting9-34Overtravel (OT)Forward or reverse run prohibited signal is input.Check the external power supply (+24 V) voltage for the input s

Pagina 259 - 6.19 Origin Setting (Fn020)

9.4 Troubleshooting Malfunction Based on Operation and Conditions of the Servomotor9-359TroubleshootingPosition Error (Without Alarm)Noise interferen

Pagina 260 - 6.20 Software Reset (Fn030)

10-110Appendix10Appendix10.1 List of Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-210.1.1 Utility

Pagina 261 - 6.21 EasyFFT (Fn206)

10 Appendix10.1.1 Utility Functions10-210.1 List of Parameters10.1.1 Utility FunctionsThe following list shows the available utility functions.Note:

Pagina 262

10.1 List of Parameters10-310Appendix10.1.2 ParametersParameterNo.SizeNameSetting RangeUnitsFactory SettingWhen EnabledClassi-ficationProfileReferenc

Pagina 263 - 6.21 EasyFFT (Fn206)

10 Appendix10.1.2 Parameters10-4Pn0022Application Function Select Switch 20000 to 4113 − 0011 After restart Setup −−∗1. For details, refer to Σ-V Se

Pagina 264

10.1 List of Parameters10-510AppendixPn0062Application Function Select Switch 60000 to 005F − 0002 Immediately Setup − 5.1.3Pn0072Application Functio

Pagina 265

10 Appendix10.1.2 Parameters10-6Pn0082Application Function Select Switch 80000 to 7121 − 4000 After restart Setup −−Pn0092Application Function Selec

Pagina 266

10.1 List of Parameters10-710AppendixPn00B2Application Function Select Switch B0000 to 1111 − 0000 After restart Setup −−Pn00C2Application Function S

Pagina 267

10 Appendix10.1.2 Parameters10-8Pn00D2Application Function Select Switch D0000 to 1001 − 0000 Immediately Setup − –Pn0812Application Function Select

Pagina 268 - Monitor Displays (Un)

1 Outline1.4.11 Three-phase 200 V SGDV-590A21A, -780A21A Models1-141.4.11 Three-phase 200 V SGDV-590A21A, -780A21A Models1.4.12 Three-phase 400 V, S

Pagina 269 - 7.1 List of Monitor Displays

10.1 List of Parameters10-910AppendixPn10B2Application Function for Gain Select Switch0000 to 5334 − 0000 −−−−Pn10C 2Mode Switch (torque refer-ence)0

Pagina 270 - 7.2 Viewing Monitor Displays

10 Appendix10.1.2 Parameters10-10Pn1392Automatic Gain Changeover Related Switch 10000 to 0052 − 0000 Immediately Tuning − 5.8.1Pn13D 2 Current Gain

Pagina 271 - OFF (open)

10.1 List of Parameters10-1110AppendixPn143 2Model Following Control Bias (Forward Direction)0 to 10000 0.1% 1000 Immediately Tuning −−Pn144 2Model F

Pagina 272

10 Appendix10.1.2 Parameters10-12Pn1602Anti-Resonance Control Related Switch0000 to 0011 − 0010 Immediately Tuning −5.3.1, 5.4.1, 5.5.1, 5.7.1Pn161

Pagina 273 - ON: Transistor ON

10.1 List of Parameters10-1310AppendixPn2072Position Control Function Switch0000 to 2210 − 0010 After restart Setup −−Pn20A 4Number of External Scale

Pagina 274 - ON (short-circuited)

10 Appendix10.1.2 Parameters10-14Pn2302Position Control Expanded Function Switch0000 to 0001 – 0000 After reset Setup – 5.8.6Pn231 4Backlash Compens

Pagina 275 - Fully-closed Loop Control

10.1 List of Parameters10-1510AppendixPn402 2 Forward Torque Limit 0 to 800 1% 800 Immediately Setup −4.6.1Pn403 2 Reverse Torque Limit 0 to 800 1% 8

Pagina 276 - 8.1.1 System Configuration

10 Appendix10.1.2 Parameters10-16Pn424 2Torque Limit at Main Circuit Vo l t a g e D r o p0 to 100 1% 50 Immediately Setup −4.3.7Pn425 2Release Time

Pagina 277

10.1 List of Parameters10-1710AppendixPn50A2 Input Signal Selection 10000 to FFF1− 1881 After restart Setup −−(cont’d)ParameterNo.SizeNameSetting Ran

Pagina 278 - 8.1.3 Serial Converter Unit

10 Appendix10.1.2 Parameters10-18Pn50B2 Input Signal Selection 20000 to FFFF−8882 After restart Setup − –(cont’d)ParameterNo.SizeNameSetting RangeUn

Pagina 279

1.4 SERVOPACK Internal Block Diagrams1-151Outline1.4.13 Three-phase 400 V, SGDV-8R4D21A, -120D21A Models1.4.14 Three-phase 400 V, SGDV-170D21A ModelL

Pagina 280 - D-sub 15-pin connector

10.1 List of Parameters10-1910AppendixPn50E2 Output Signal Selection 1 0000 to 3333 − 0000 After restart Setup −−Pn50F2 Output Signal Selection 2 000

Pagina 281 - Renishaw external encoder

10 Appendix10.1.2 Parameters10-20Pn5102 Output Signal Selection 3 0000 to 0333 − 0000 After restart Setup −−(cont’d)ParameterNo.SizeNameSetting Rang

Pagina 282

10.1 List of Parameters10-2110AppendixPn5112 Input Signal Selection 50000 to FFFF− 6543 After restart Setup − 3.3.1(cont’d)ParameterNo.SizeNameSettin

Pagina 283

10 Appendix10.1.2 Parameters10-22Pn5122 Output Signal Inverse Setting 0000 to 0111 − 0000 After restart Setup − 3.3.2Pn517 2 Reserved (Do not change

Pagina 284

10.1 List of Parameters10-2310AppendixPn5302Program JOG Operation Related Switch0000 to 0005 − 0000 Immediately Setup − 6.5Pn531 4Program JOG Movemen

Pagina 285

10 Appendix10.1.2 Parameters10-24Pn621 to Pn628*11–SERVOPACK: Safety Module Parameters––– ––––Pn8002 Communications Control – – 1040 Immediately Set

Pagina 286 - 8 Fully-closed Loop Control

10.1 List of Parameters10-2510AppendixPn8012Application Function Select 6(Software LS)– – 0003 Immediately Setup − 4.3.3Pn803 2 Origin Range 0 to 250

Pagina 287

10 Appendix10.1.2 Parameters10-26Pn80E 22nd Linear Deceleration Constant1 to 6553510000referenceunit/s2100Immediately*5Setup −*1Pn80F 2Deceleration

Pagina 288 - (2) Setting Parameter Pn002.3

10.1 List of Parameters10-2710AppendixPn81E2Input Signal Monitor Selection– – 0000 Immediately SetupM2*10–Pn81F2 Command Data Allocation – – 0010 Aft

Pagina 289

10 Appendix10.1.2 Parameters10-28Pn824 2Option Monitor 1 Selection – –0000 Immediately Setup−*10000HMotor rotating speed [1000000H/overspeed detecti

Pagina 290 - (1) Setting Example

1 Outline1.4.15 Three-phase 400 V, SGDV-210D21A, -260D21A Models1-161.4.15 Three-phase 400 V, SGDV-210D21A, -260D21A Models1.4.16 Three-phase 400 V,

Pagina 291

10.1 List of Parameters10-2910AppendixPn825 2Option Monitor 2 Selection – – 0000 ImmediatelySetup −*10000Hto 0084HSame as Option Monitor 1 Selection.

Pagina 292

10 Appendix10.1.2 Parameters10-30Pn82C2 Option Field Allocation 30000 to 1F1F– 1F1E After restart SetupM2*10–Pn82D2 Option Field Allocation 40000 to

Pagina 293 - 00000 1010 1

10.1 List of Parameters10-3110AppendixPn8332 Motion Setting 0000 to 0001 – 0000 After restart Setup –*1Pn834 41st Linear Acceleration Constant 21 to

Pagina 294 - 8.3.5 Electronic Gear

10 Appendix10.1.2 Parameters10-32Pn8522Latch Sequence Signal 1 to 4 Setting0000 to 3333 – 0000 Immediately Setup –*1Pn8532Latch Sequence Signal 5 to

Pagina 295 - 8.3.6 Alarm Detection

10.1 List of Parameters10-3310AppendixPn8602SVCMD_IO (input signal monitor) Allocation 10000 to 1717 – 0000 Immediately SetupM3*9–Pn8612SVCMD_IO (inp

Pagina 296 - 8.3.7 Analog Monitor Signal

10 Appendix10.1.2 Parameters10-34Pn8632SVCMD_IO (input signal monitor) Allocation 40000 to 1717 – 0000 Immediately SetupM3*9–Pn8642SVCMD_IO (input s

Pagina 297 - Troubleshooting

10.1 List of Parameters10-3510AppendixPn8682SVCMD_IO (output signal monitor) Allocation 10000 to 1717 – 0000 Immediately SetupM3*9–Pn8692SVCMD_IO (ou

Pagina 298 - 9.1.1 List of Alarms

10 Appendix10.1.2 Parameters10-36Pn882 2Transmission Cycle Setting Monitor [0.25 μs] (for maintenance, read only)0 to FFFFH – 0 Immediately Setup –

Pagina 299 - 9.1 Alarm Displays

10.1 List of Parameters10-3710Appendix10.1.3 MECHATROLINK-III Common ParametersThe following list shows the common parameters used by all devices for

Pagina 300 - 9.1.1 List of Alarms

10 Appendix10.1.3 MECHATROLINK-III Common Parameters10-3826PnA4C4 Forward Software Limit–1073741823 to 10737418231 reference unit 1073741823Immedi-a

Pagina 301

1.5 Examples of Servo System Configurations1-171Outline1.5 Examples of Servo System ConfigurationsThis section describes examples of basic servo syst

Pagina 302

10.1 List of Parameters10-3910Appendix49PnA924Compliance Unit System (read only) – –0601011FH –Unit System Related ParametersSpeedBit 0 reference un

Pagina 303

10 Appendix10.1.3 MECHATROLINK-III Common Parameters10-4081PnB024Exponential Function Accel/Decel Time Constant0 to 510000μs[0.1 ms]0Immedi-ately*6C

Pagina 304 - × Pn901 >

10.1 List of Parameters10-4110Appendix89PnB124Monitor Selection for SEL_MON1 (CMN1) 0 to 6 –0Immedi-atelyCommand Related Parameters0000H TPOS (Target

Pagina 305

10 Appendix10.1.3 MECHATROLINK-III Common Parameters10-428APnB144Monitor Selection for SEL_MON2 (CMN2) 0 to 6 –0Immedi-atelyCommand Related Paramete

Pagina 306

10.1 List of Parameters10-4310Appendix91PnB224Servo Command Status Field Enabled/Disabled (read only) –00FFF3F33H –Command Related ParametersBit 0 CM

Pagina 307

10 Appendix10-4493PnB264I/O Bit Enabled/Disabled (Input) (read only) ––FF0FFEFEH –Command Related ParametersBit 0 Reserved (0: Disabled) Bit 1 DEC (1

Pagina 308

10.2 List of Monitor Displays10-4510Appendix10.2 List of Monitor DisplaysThe following list shows the available monitor displays.∗1. For details, ref

Pagina 309

10 Appendix10-4610.3 Parameter Recording TableUse the following table for recording parameters.Note: Pn10B, Pn170, and Pn408 have two kinds of digits

Pagina 310

10.3 Parameter Recording Table10-4710AppendixPn139 0000Automatic Gain Changeover Related Switch 1ImmediatelyPn13D 2000 Current Gain Level Immediately

Pagina 311

10 Appendix10-48Pn306 0 Soft Start Deceleration Time ImmediatelyPn310 0000 Vibration Detection Switch ImmediatelyPn311 100 Vibration Detection Sensib

Pagina 312

1 Outline1.5.2 Connecting to SGDV-A21 SERVOPACK1-181.5.2 Connecting to SGDV-A21 SERVOPACK(1) Using a Three-phase, 200-V Power Supply∗1. Use

Pagina 313

10.3 Parameter Recording Table10-4910AppendixPn50F 0100 Output Signal Selection 2 After restartPn510 0000 Output Signal Selection 3 After restartPn51

Pagina 314

10 Appendix10-50Pn808 0 Absolute Encoder Origin OffsetImmediately∗1Pn80A 100 1st Linear Acceleration ConstantImmediately∗2Pn80B 100 2nd Linear Accele

Pagina 315

10.3 Parameter Recording Table10-5110AppendixPn836 100 2nd Linear Acceleration Constant 2Immediately∗2Pn838 0Acceleration Constant Switching Speed 2I

Pagina 316

10 Appendix10-52Pn88A 0MECHATROLINK Receive Error Counter Monitor (for maintenance, read only)ImmediatelyPn890 to Pn8A60Command Data Monitor at Alarm

Pagina 317

10.3 Parameter Recording Table10-5310Appendix28PnA50-1073741823Reverse Software Limit Immediately29PnA520 Reserved (Do not use.) Immediately41PnA820

Pagina 318

10 Appendix10-5485PnB0A500Value con-verted refer-ence/s into 10-3 min-1Homing Creep Speed Immediately86PnB0C100 Final Travel Distance for Homing Imme

Pagina 319 - 9.2 Warning Displays

IndexIndex-1IndexSymbols/BK - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-11/CLT - - - - - - - - - - - - - -

Pagina 320 - 9.2.1 List of Warnings

IndexIndex-2european directives- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - xivexamples of encoder connection - - - - - - - - - -

Pagina 321 - 9.2 Warning Displays

IndexIndex-3positioning near signal - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-54P-OT - - - - - - - - - - - - - - - - - - - - - - -

Pagina 322

Revision HistoryThe revision dates and numbers of the revised manuals are given on the bottom of the back cover.MANUAL NO.ޓSIEP S800000 64APublished i

Pagina 323

1.5 Examples of Servo System Configurations1-191Outline(2) Using a Single-phase, 200-V Power SupplyThe Σ-V Series 200 V SERVOPACK generally specifies

Pagina 324

April 2010 23.5 Revision: Diagram4.7.5 (2) Revision: Description of the initial incremental pulses5.3.2, 5.4.2, 5.5.2, 5.7.1Addition: Description of C

Pagina 325

IRUMA BUSINESS CENTER (SOLUTION CENTER)480, Kamifujisawa, Iruma, Saitama, 358-8555, JapanPhone 81-4-2962-5151 Fax 81-4-2962-6138http://www.yaskawa

Pagina 326

iv Notation Used in this Manual• Notation for Reverse SignalsThe names of reverse signals (i.e., ones that are valid when low) are written with a

Pagina 327 - Conditions of the Servomotor

1 Outline1.5.3 Connecting to SGDV-D21A SERVOPACK1-201.5.3 Connecting to SGDV-D21A SERVOPACK∗1. Use a 24-VDC power supply with double insulatio

Pagina 328

1.6 SERVOPACK Model Designation1-211Outline1.6 SERVOPACK Model DesignationThis section shows SERVOPACK model designation.∗1. These amplifiers can be

Pagina 329

1 Outline1-221.7 Inspection and MaintenanceThis section describes the inspection and maintenance of SERVOPACK.(1) SERVOPACK InspectionFor inspection

Pagina 330

2-12Panel Display and Operation of Digital Operator2Panel Display andOperation of Digital Operator2.1 Panel Display . . . . . . . . . . . . . . . .

Pagina 331

2 Panel Display and Operation of Digital Operator2.1.1 Status Display2-22.1 Panel DisplayThe servo status can be checked on the panel display of the

Pagina 332 - Appendix

2.2 Operation of Digital Operator2-32Panel Display and Operation of Digital Operator2.2 Operation of Digital OperatorOperation examples of utility fu

Pagina 333 - 10.1.1 Utility Functions

2 Panel Display and Operation of Digital Operator2.4.1 Parameter Classification2-42.4 Parameters (Pn)This section describes the classifications,

Pagina 334 - 10.1.2 Parameters

2.4 Parameters (Pn)2-52Panel Display and Operation of Digital Operator• Notation Example2.4.3 Setting Parameters(1) How to Make Numeric Settings U

Pagina 335

2 Panel Display and Operation of Digital Operator2.4.3 Setting Parameters2-6(2) How to Select Functions Using ParametersThe following example shows

Pagina 336

2.5 Monitor Displays (Un)2-72Panel Display and Operation of Digital Operator2.5 Monitor Displays (Un)The monitor displays can be used for monit

Pagina 337

v Manuals Related to the Σ-V SeriesRefer to the following manuals as required. TrademarksMECHATROLINK is a trademark of the MECHATROLINK Members Ass

Pagina 338

3-13Wiring and Connection3Wiring and Connection3.1 Main Circuit Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 339 - 1 Detects overtravel warning

3 Wiring and Connection3.1.1 Main Circuit Terminals3-23.1 Main Circuit WiringThe names and specifications of the main circuit terminals are given be

Pagina 340

3.1 Main Circuit Wiring3-33Wiring and Connection∗1. Do not short-circuit between B1/ and B2. It may damage the SERVOPACK.∗2. The DC reactor connecti

Pagina 341

3 Wiring and Connection3.1.2 Using a Standard Power Supply (Single-phase 100 V, Three-phase 200 V, or Three-phase 400 V)3-4(2) Main Circuit WiresThi

Pagina 342

3.1 Main Circuit Wiring3-53Wiring and Connection(3) Typical Main Circuit Wiring ExamplesNote the following points when designing the power ON sequenc

Pagina 343

3 Wiring and Connection3.1.2 Using a Standard Power Supply (Single-phase 100 V, Three-phase 200 V, or Three-phase 400 V)3-6 Three-phase 200 V, SGDV

Pagina 344

3.1 Main Circuit Wiring3-73Wiring and Connection Three-phase 400 V, SGDV-D• SGDV-1R9D, -3R5D, -5R4D, -8R4D, -120D, -170D• SGDV-210D, -260D, -280D

Pagina 345

3 Wiring and Connection3.1.2 Using a Standard Power Supply (Single-phase 100 V, Three-phase 200 V, or Three-phase 400 V)3-8(4) Power Supply Capaciti

Pagina 346

3.1 Main Circuit Wiring3-93Wiring and Connection(5) How to Select Molded-case Circuit Breaker and Fuse CapacitiesThe following table shows the SERVOP

Pagina 347

3 Wiring and Connection3.1.2 Using a Standard Power Supply (Single-phase 100 V, Three-phase 200 V, or Three-phase 400 V)3-102. The following restric

Pagina 348

vi Safety InformationThe following conventions are used to indicate precautions in this manual. Failure to heed precautions pro-vided in this man

Pagina 349

3.1 Main Circuit Wiring3-113Wiring and Connection3.1.3 Using the SERVOPACK with Single-phase, 200 V Power InputSome models of Σ-V series three-phase

Pagina 350

3 Wiring and Connection3.1.3 Using the SERVOPACK with Single-phase, 200 V Power Input3-12(3) Main Circuit Wire for SERVOPACKs∗ The official model nu

Pagina 351

3.1 Main Circuit Wiring3-133Wiring and Connection(5) Power Supply Capacities and Power LossesThe following table shows SERVOPACK’s power supply capac

Pagina 352 - 10.1 List of Parameters

3 Wiring and Connection3.1.4 Using the SERVOPACK with a DC Power Input3-143.1.4 Using the SERVOPACK with a DC Power Input(1) Parameter SettingWhen u

Pagina 353

3.1 Main Circuit Wiring3-153Wiring and Connection(3) Wiring Example with DC Power Supply Input 200-V SERVOPACK SGDV-A∗ Terminal names differ depe

Pagina 354 - Vo l t a g e

3 Wiring and Connection3.1.5 Using More Than One SERVOPACK3-163.1.5 Using More Than One SERVOPACKThis section shows an example of the wiring and the

Pagina 355

3.1 Main Circuit Wiring3-173Wiring and Connection3.1.6 General Precautions for WiringTo ensure safe, stable application of the servo system, observe

Pagina 356

3 Wiring and Connection3.2.1 I/O Signal (CN1) Names and Functions3-183.2 I/O Signal ConnectionsThis section describes the names and functions of I/O

Pagina 357 - 10.1.2 Parameters

3.2 I/O Signal Connections3-193Wiring and Connection(2) Output SignalsNote: The allocation of the output signals (/SO1 to /SO3) can be changed. For d

Pagina 358

3 Wiring and Connection3.2.3 Example of I/O Signal Connections3-203.2.3 Example of I/O Signal ConnectionsThe following diagram shows a typical conne

Pagina 359

viiSafety PrecautionsThis section describes important precautions that must be followed during storage, transportation, installation, wiring, operatio

Pagina 360

3.3 I/O Signal Allocations3-213Wiring and Connection3.3 I/O Signal AllocationsThis section describes the I/O signal allocations.3.3.1 Input Signal Al

Pagina 361

3 Wiring and Connection3.3.1 Input Signal Allocations3-22∗ Always set to "Invalid."Input Signal Names and ParametersValid-ity LevelInput S

Pagina 362

3.3 I/O Signal Allocations3-233Wiring and Connection3.3.2 Output Signal AllocationsOutput signals are allocated as shown in the following table.Refer

Pagina 363

3 Wiring and Connection3.4.1 Sequence Input Circuit3-243.4 Examples of Connection to Host ControllerThis section shows examples of SERVOPACK I/O sig

Pagina 364

3.4 Examples of Connection to Host Controller3-253Wiring and Connection(2) Safety Input CircuitAs for wiring input signals for safety function, input

Pagina 365

3 Wiring and Connection3.4.2 Sequence Output Circuit3-26(2) Line Driver Output CircuitCN1 connector terminals, 17-18 (phase-A signal), 19-20 (phase-

Pagina 366

3.5 Wiring MECHATROLINK-III Communications3-273Wiring and Connection3.5 Wiring MECHATROLINK-III CommunicationsThe following diagram shows an example

Pagina 367

3 Wiring and Connection3.6.1 Encoder Signal (CN2) Names and Functions3-283.6 Encoder ConnectionThis section describes the encoder signal (CN2) names

Pagina 368 - –1073741823

3.6 Encoder Connection3-293Wiring and Connection(2) Absolute Encoder∗1. The pin arrangement for wiring connectors varies in accordance with the servo

Pagina 369

3 Wiring and Connection3.7.1 Connecting Regenerative Resistors3-303.7 Connecting Regenerative ResistorsIf the built-in regenerative resistor is insu

Pagina 370

viii Storage and Transportation Installation CAUTION• Do not store or install the product in the following locations.Failure to observe this cau

Pagina 371

3.7 Connecting Regenerative Resistors3-313Wiring and Connection(3) SERVOPACKs: Model SGDV-470A, -550A, -590A, -780A, -210D, -260D, -280D, -370DNo bui

Pagina 372

3 Wiring and Connection3.7.2 Setting Regenerative Resistor Capacity3-323.7.2 Setting Regenerative Resistor CapacityWhen using an external regenerati

Pagina 373

3.8 Noise Control and Measures for Harmonic Suppression3-333Wiring and Connection3.8 Noise Control and Measures for Harmonic SuppressionThis section

Pagina 374

3 Wiring and Connection3.8.1 Wiring for Noise Control3-34(1) Noise FilterThe SERVOPACK has a built-in microprocessor (CPU), so protect it from exter

Pagina 375

3.8 Noise Control and Measures for Harmonic Suppression3-353Wiring and Connection3.8.2 Precautions on Connecting Noise FilterThis section describes t

Pagina 376 - 10.2 List of Monitor Displays

3 Wiring and Connection3.8.3 Connecting a Reactor for Harmonic Suppression3-36Connect the noise filter ground wire directly to the ground plate.Do n

Pagina 377

4-14Operation4Operation4.1 MECHATROLINK-III Communications Settings . . . . . . . . . . . . . . . . . . . .4-34.1.1 Setting Switches S1, S2, and S3

Pagina 378

4 Operation 4-24.7 Absolute Encoders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-354.7.1 Connecting the A

Pagina 379

4.1 MECHATROLINK-III Communications Settings4-34Operation4.1 MECHATROLINK-III Communications SettingsThis section describes the switch settings neces

Pagina 380

4 Operation4.3.1 Servomotor Rotation Direction4-44.2 MECHATROLINK-III CommandsFor information on the MECHATROLINK-III commands, refer to Σ-V Series

Pagina 381 - Immediately

ix Wiring CAUTION• Be sure to wire correctly and securely.Failure to observe this caution may result in motor overrun, injury, or malfunction.• Do no

Pagina 382

4.3 Basic Functions Settings4-54Operation4.3.2 OvertravelThe overtravel limit function forces movable machine parts to stop if they exceed the allowa

Pagina 383

4 Operation4.3.2 Overtravel4-6(3) Servomotor Stopping Method When Overtravel is UsedThere are three servomotor stopping methods when an overtravel i

Pagina 384

4.3 Basic Functions Settings4-74Operation(4) Overtravel Warning FunctionThis function detects an overtravel warning (A.9A0) if overtravel occurs whil

Pagina 385

4 Operation4.3.3 Software Limit Settings4-84.3.3 Software Limit SettingsThe software limits set limits in software for machine movement that do not

Pagina 386

4.3 Basic Functions Settings4-94Operation4.3.4 Holding BrakesA holding brake is a brake used to hold the position of the movable part of the machine

Pagina 387

4 Operation4.3.4 Holding Brakes4-10Note: The above operation delay time is an example when the power supply is turned ON and OFF on the DC side.Be s

Pagina 388

4.3 Basic Functions Settings4-114Operation(2) Brake Signal (/BK) SettingThis output signal controls the brake. The allocation of the /BK signal can b

Pagina 389 - Revision History

4 Operation4.3.4 Holding Brakes4-12(3) Brake Signal (/BK) AllocationUse parameter Pn50F.2 to allocate the /BK signal.(4) Brake ON Timing after the S

Pagina 390

4.3 Basic Functions Settings4-134Operation(5) Brake Signal (/BK) Output Timing during Servomotor RotationIf an alarm occurs while the servomotor is r

Pagina 391

4 Operation4.3.5 Stopping Servomotors after SV_OFF Command or Alarm Occurrence4-144.3.5 Stopping Servomotors after SV_OFF Command or Alarm Occurrenc