Object ID Object Name
Modbus
Address
Precision Range Units PV Access
AV13 Output Power 0047H
XXXX.X
(for drives rated
above 11 kVA)
XXX.XX
(for drives rated
11 kVA or
lower)
kW R
AV14 Torque Reference 0048H XXXX.X % R
AV15 MF Input Status 002BH R
AV16 Drive Status 2 002CH R
AV17 MF Output Status 002DH R
AV18 DC Bus Voltage 0031H XXXXX Volts R
AV19 PI Feedback Level 0038H XXXX.X % R
AV20 PI Input Level 0039H XXXX.X % R
AV21 PI Output Level 003AH XXXX.X % R
AV22 Drive SW Num 004DH XXXXX R
AV23 Bypass SW Num 8791H XXXXX R
AV24 Comm Error Detail 003DH R
AV25 KVA Setting 003EH XXXXX R
AV26 Control Method 0043H XXXXX R
AV27 Accel Time 0200H XXXX.X 0.0 to 6000.0 Sec W
AV28 Decel Time 0201H XXXX.X 0.0 to 6000.0 Sec W
AV29
<1>
Parameter Number XXXXX 0 to FFFFH W
AV30
<1>
Parameter Data XXXXX 0 to FFFFH W
AV31 Motor Current 8780H XXXX.X Amps R
AV32 120 V to Kx Coils 8790H XXXXX Volts R
AV33
<2>
Drive kWH
0x005C and
0x005D
XXXXXXX.X 0.0 to 32767999.9 kWH R
<1> Refer to Accessing Bypass Parameters and the Enter Command on page 370 for an explanation of how to read and write drive parameters not
listed in the analog or binary objects.
<2> Available in bypass controller software versions VST800298 and later.
u
Binary Input Objects
Table C.7 Binary Input Objects
Object ID Object Name
Modbus
Address
Active Text Inactive Text PV Access
BI1 Input Terminal 1 002BH:bit 0 ON OFF R
BI2 Input Terminal 2 002BH:bit 1 ON OFF R
BI3 Input Terminal 3 002BH:bit 2 ON OFF R
BI4 Input Terminal 4 002BH:bit 3 ON OFF R
BI5 Input Terminal 5 002BH:bit 4 ON OFF R
BI6 Input Terminal 6 002BH:bit 5 ON OFF R
BI7 Input Terminal 7 002BH:bit 6 ON OFF R
BI8 Multi-Function Out 1 0020H:bit 5 ON OFF R
BI9 Multi-Function Out 2 0020H:bit 6 ON OFF R
BI10 BYP DI-1 STAT 8781H: bit 0 ON OFF R
BI11 BYP DI-2 STAT 8781H: bit 1 ON OFF R
BI12 BYP DI-3 STAT 8781H: bit 2 ON OFF R
BI13 BYP DI-4 STAT 8781H: bit 3 ON OFF R
BI14 BYP DI-5 STAT 8781H: bit 4 ON OFF R
BI15 BYP DI-6 STAT 8781H: bit 5 ON OFF R
C.6 BACnet Objects Supported