n3-13: Overexcitation Deceleration Gain
Multiplies a gain to the V/f pattern output value during Overexcitation Deceleration to determine the level of overexcitation.
The drive returns to the normal V/f value after the motor has stopped or when it is accelerating to the frequency reference.
No. Name Setting Range Default
n3-13 Overexcitation Deceleration Gain 1.00 to 1.40 1.10
The optimum setting for n3-13 depends on the motor flux saturation characteristics.
Gradually increase the gain to 1.25 or 1.30 to improve the braking power of Overexcitation Deceleration.
Lower n3-13 when flux saturation characteristics cause overcurrent. A high setting sometimes causes overcurrent (oC),
motor overload (oL1), or drive overload (oL2). Lowering n3-21 can also help remedy these problems.