Register No. Contents
00D9H
oFA1x Contents (CN5)
bit 0 Option RAM Fault (oFA10)
bit 1 Option Operation Mode Fault (SLMoD) (oFA11)
bit 2 Drive Receive CRC Error (oFA12)
bit 3 Drive Receive Frame Error (oFA13)
bit 4 Drive Receive Abort Error (oFA14)
bit 5 Option Receive CRC Error (oFA15)
bit 6 Option Receive Frame Error (oFA16)
bit 7 Option Receive Abort Error (oFA17)
bit 8 to F Reserved
00DAH Reserved
00DBH
oFA3x Contents (CN5)
bit 0 Comm. ID Error (oFA30)
bit 1 Model Code Error (oFA31)
bit 2 Sumcheck Error (oFA32)
bit 3 Comm. option timeout waiting for response (oFA33)
bit 4 MEMOBUS Timeout (oFA34)
bit 5 Drive timeout waiting for response (oFA35)
bit 6 CI Check Error (oFA36)
bit 7 Drive timeout waiting for response (oFA37)
bit 8 Control Command Selection Error (oFA38)
bit 9 Drive timeout waiting for response (oFA39)
bit A Control Response Selection 1 Error (oFA40)
bit B Drive timeout waiting for response (oFA41)
bit C Control Response Selection 2 Error (oFA42)
bit D Control Response Selection Error (oFA43)
bit E, bit F Reserved
00DCH to 00E9H Reserved
00EAH
Fault Contents 9
bit 0 Time Not Set (TIM)
bit 1 Oper Battery Low (bAT)
bit 2 Time Data Err (TdE)
bit 3 Time Interval Error (TIE)
bit 4 Overvoltage 2 (ov2)
bit 5 Reserved
bit 6 External Fan Fault (Fn1)
bit 7 to F Reserved
00EBH to 00FFH Reserved
0100H to 2FFFH Reserved
3000H to 3003H
Used for Various Monitors U5-oo. Refer to U: Monitors on page 334 for details.
3004H to 3007H Reserved
3008H to 3028H
Used for Various Monitors U2-oo, U3-oo, U5-oo. Refer to U: Monitors on page 334 for details.
3029H to 302EH Reserved
302FH to 83FFH Reserved
D.9 MEMOBUS/Modbus Data Table
396
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual