Yaskawa Sigma-5 Large Capacity Users Manual: Design and Ma Manuale Utente Pagina 264

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 263
6 Utility Functions (Fn)
6-22
(1) Preparation
There are no tasks that must be performed before the execution.
(2) Operating Procedure
Follow the steps to set enable or disable writing.
Setting values are as follows:
"P.0000": Write permitted (Releases write prohibited mode.) [Factory setting]
"P.0001": Write prohibited (Parameters become write prohibited from the next power ON.)
Note: To make the setting available, change the setting to P.0000 as shown in step 3.
Step Display after Operation Keys Operation
1
Press the Key to view the main menu for the
utility function.
Use the or Key to move through the list and
select Fn010.
2
Press the Key. The display changes to the Fn010
execution display.
3
Press the or Key to select one of the follow-
ing settings.
P.0000: Write permitted [Factory setting]
P.0001: Write prohibited
4
Press the Key. The setting value is written into
the SERVOPACK, and the status display changes as
follows: "BB" to "DONE" to "BB."
Note: Saved settings will be enabled after the SER-
VOPACK is restarted.
5 To enable the change in the setting, turn the power OFF and ON again.
BB FUNCTION
Fn00F:Cur ManuAdj
Fn010:Prm Protect
Fn011:Motor Info
Fn012:Soft Ver
BB
Parameter
Write Protect
P. 0000
BB
Parameter
Write Protect
P. 0001
BB
Parameter
Write Protect
P. 0001
Vedere la pagina 263
1 2 ... 259 260 261 262 263 264 265 266 267 268 269 ... 389 390

Commenti su questo manuale

Nessun commento