21
Effective when output terminal function selections n40,
are set to “frequency detection (setting : 4 or 5).
“Frequency detection” turns ON when output frequency
is higher or lower than the frequency detection level
(n58).
Frequency detection 1
(Output frequency Frequency
detection level)
(Set n40 to “4”)
FREQUENCY DETECTION
LEVEL (Hz)
(n58)
OUTPUT
FREQUENCY
FREQUENCY
DETECTION
SIGNAL
RELEASE
WIDTH –2Hz
ON
Frequency detection 2
(Output frequency Frequency
detection level)
(Set n40 to “5”)
FREQUENCY DETECTION
LEVEL (Hz)
(n58)
OUTPUT
FREQUENCY
FREQUENCY
DETECTION
SIGNAL
ONON
RELEASE
WIDTH +2Hz
This function allows the prohibition or “jumping” of
critical frequencies so that the motor can operate without
resonance caused by machine systems. This function is
also used for dead band control. Setting the value to
0.0Hz disables this function.
Set jump frequency 1, 2 or 3 as follows:
n49 n50
If this condition is not
satisfied the inverter
displays for one
second and restores the
data to original settings.
Note : Gradually changes without
jumping during accel/decel.
n51
n49
n50
n51
OUTPUT FREQUENCY
FREQUENCY REF.
To operate coasting motor without trip, use the speed
search command or DC injection braking at start.
Speed search command
Restarts a coasting motor without stopping it. This
function enables smooth switching between motor
commercial power supply operation and inverter
operation.
Set input terminal function selection (n36 to n39) to
“14” (search command from maximum output
frequency) or “15” (search command from set
frequency).
Build a sequence so that FWD (REV) run command is
input at the same time as the search command or after
the search command. If the run command is input
before the search command, the search command
becomes disabled.
ON
ON
0.5s OR MORE
FWD (REV) RUN
COMMAND
SEARCH COMMAND
OUTPUT FREQUENCY
AGREED SPEED
DETECTION
MAX. OUTPUT FREQUENCY
OR FREQUENCY REF.
AT RUN COMMAND
INPUT
MIN. BASEBLOCK
TIME (0.5sec)
SPEED SEARCH
OPERATION
Time chart at search command input
DC injection braking at start
(n52, n54)
Restarts a coasting motor after
stopping it. Set DC injection
braking time at start in n54 in
units of 0.1 second. Set DC
injection braking current in
n52 in units of 1%. When the
setting of n54 is “0,” DC
injection braking is not performed and acceleration
starts from the minimum output frequency.
n14
MIN. OUTPUT
FREQUENCY
n54
DC INJECTION BRAKING
TIME AT START
Frequency detection
Frequency detection level
N58
Avoiding resonance
Jump frequency 1, 2
Jump width
N51
N50N49
Operating coasting motor without trip
Speed search command
Input terminal function selection to
DC injection braking at start
DC injection braking current
DC injection braking time at start
N54
N52
N39N36
Commenti su questo manuale