Type Terminal Name Function (Signal Level)
Main Circuit
Control Circuit
InputOutput
Sequence
Frequency
reference
Multi-function
†
contact output
R/L1,
S/L2,
T/L3
U/T1,
V/T2,
W/T3
+2, +1
+1, –
S1
S2
S3
S4
S5
FS
FC
MA
MB
MC
AM
AC
AC power supply
input
Inverter output
DC reactor
connection
DC power supply input
Grounding
Forward run input
Multi-function input selection 2
Multi-function input selection 3
Multi-function input selection 4
Multi-function input selection 5
Power for frequency setting
Frequency reference common
NO contact output
NC contact output
Contact output common
Analog monitor common
Analog monitor output
Inverter output
Use main circuit power input. (Use terminals R/L1
and S/L2 for single -phase inverters. Never use
terminal T/L3.)
When connecting optional DC reactor, remove the
main circuit short-circuit bar between +2 and +1.
For grounding (according to the local grounding
code)
DC power supply input (+1: positive -: negative) *
Factory setting: External fault (NO contact)
Factory setting: Multi-step speed reference 1
+12V (permissible current 20mA max.)
0V
Closed: FWD run, open: REV run
Factory setting closed: REV run, open: FWD run
Factory setting: Fault reset
Factory setting: running
Factory setting:
Output frequency 0 to +10VDC
0V
Photo-coupler
insulation,
24VDC,
8mA
Contact capacity
250VAC 1A or less,
30VDC 1A or less
0 to +10VDC, 2mA or
less,
8-bit resolution
Multi-function input
selection common
SC
For control signal
FR
Master speed frequency
reference
0 to +10VDC (20kΩ) or 4 to 20mA (250kΩ) or 0 to
20mA (250Ω) (1/1000 resolution)